Fancoil TFCU Series
Electrical Connections
Electrical Connections
All electrical connections must be made
by qualified personnel, in accordance with
applicable regulations and with Low-Voltage
Regulations.
Only copper conductors must be used in order
to prevent galvanic corrosion and/or the contact
point from overheating.
Before connecting the unit, disconnect from the
mains. Connect the unit with protective earthing.
TROX España shall not be held responsible for
incorrect electrical connections.
Units have been designed to work exclusively
with a nominal supply voltage of 230 V, 50/60Hz
single-phase, and a control voltage of 0-10 V.
TFCUP
Size
Battery type
1
2
3
4
4,5
5
6
7
Cold/hot
2 TP
0,8
1,2
1,3
1,7
2,2
2,0
2,5
2,9
Cold
4 TP
0,8
1,2
1,3
1,7
2,2
2,0
2,5
2,9
4 TD
1,1
1,6
1,8
2,2
2,8
2,7
3,4
3,9
Hot
4 TP - TD
0,3
0,4
0,4
0,6
0,6
0,7
0,8
1,0
TFCU
Coils inner volume (l)
Size
Battery type
1
2
2,5
3
4
5
Cold/hot
0,8
1,2
1,2
1,3
1,7
2,0
Hot
0,3
0,4
0,4
0,4
0,6
0,7
Technical Specifications
TFCU/TFCUP fan coil units have been designed
to work under the following operating conditions:
▪ Heat-transfer fluid: Water or glycols
(ethylene or propylene) at a maximum
concentration of 60%.
▪ Temperature range for the heat-transfer fluid:
5–95 °C.
▪ Air temperature range: 1–40 °C.
▪ Maximum operating pressure for the coils:
16 bar/95 °C.
▪ Supply voltage: 230 V, 50/60 Hz.