Fire dampers
Correct use
FKR-EU
1
K4 – 1.1 – 10
03/2017 – DE/en
Essential characteristic: fire resistance ― size [mm]: Ø 315 to Ø 800
Supporting
construction
Shaft wall
Solid ceiling slab
Construction
•
Half-timbered wall
•
Gypsum bonded or cement bonded panel materials, fibre-
reinforced gypsum or fire rated calcium silicate boards
• d ≥ 140 mm
• Distance between casings ≥ 40 mm
• Distance to load-bearing structural elements ≥ 40 mm
•
Half-timbered wall
•
Gypsum bonded or cement bonded panel materials, fibre-
reinforced gypsum or fire rated calcium silicate boards
• d ≥ 140 mm
•
Installation kit TQ
•
Half-timbered wall
•
Gypsum bonded or cement bonded panel materials, fibre-
reinforced gypsum or fire rated calcium silicate boards
• d ≥ 115 mm
• Wall thickness increased to d ≥ 140 mm
• Distance between casings ≥ 40 mm
• Distance to load-bearing structural elements ≥ 40 mm
•
Half-timbered wall
•
Gypsum bonded or cement bonded panel materials, fibre-
reinforced gypsum or fire rated calcium silicate boards
• d ≥ 115 mm
• Wall thickness increased to d ≥ 140 mm
•
Installation kit TQ
•
Metal support structure or steel support structure
•
Gypsum bonded or cement bonded panel materials, fibre-
reinforced gypsum or fire rated calcium silicate boards
•
Cladding on one side
• d ≥ 90 mm
• Distance to load-bearing structural elements ≥ 40 mm
•
Metal support structure
•
Additional safety board
•
Gypsum bonded or cement bonded panel materials, fibre-
reinforced gypsum or fire rated calcium silicate boards
•
Cladding on one side
• with reinforcing board ≥ 90 mm
•
without metal support structure
•
Gypsum bonded or cement bonded panel materials, fibre-
reinforced gypsum or fire rated calcium silicate boards
•
Cladding on one side
• d ≥ 50 mm
• Distance to load-bearing structural elements ≥ 40 mm
• d ≥ 100 mm
• Distance between casings ≥ 40 mm
• Distance to load-bearing structural elements ≥ 40 mm
• d ≥ 100 mm
•
combined with wooden beam ceilings
• Distance between casings ≥ 40 mm
• Distance to load-bearing structural elements ≥ 40 mm
• d ≥ 100 mm
•
Combined with suspended ceiling systems (Cadolto system)
• Distance between casings ≥ 40 mm
• Distance to load-bearing structural elements ≥ 40 mm
Installation
location
in the wall
in the wall
in the wall
in the wall
in the wall
in the wall
in the wall
in the ceiling
in the ceiling
in the ceiling
Installation type
Mortar-based
installation
Dry mortarless
installation
Mortar-based
installation
Dry mortarless
installation
Mortar-based
installation
Mortar-based
installation
Mortar-based
installation
Mortar-based
installation
Mortar-based
installation
Mortar-based
installation
EI 90 (v
e
i↔o) S
EI 90 (v
e
i↔o) S
EI 30 (v
e
i↔o) S
EI 30 (v
e
i↔o) S
EI 90 (v
e
i↔o) S
EI 90 (v
e
i↔o) S
EI 90 (v
e
i↔o) S
EI 120 (h
o
i↔o) S
EI 90 (h
o
i↔o) S
EI 120 (h
o
i↔o) S
Class of
performance
(EI TT)
Lightweight
partition wall
TOC