Overriding operating mode defaults set
by the central BMS
Operating mode default settings from the central
BMS can be overridden on the control panel for the
room.
Overriding the room operating mode
temporarily
A centrally set room operating mode can be
temporarily overridden at any time using the
operating mode button on the control panel. The
operating mode selected on the room control panel
remains active unless the central BMS sets another
operating mode. If the central BMS sets a different
default operating mode, that operating mode
overrides the locally activated operating mode.
The operating mode for all room controllers is
always the operating mode that has been set last,
either by the central BMS or on the room control
panel.
Overriding the room operating mode
permanently using manual control
A centrally set room operating mode
can be permanently overridden on the
room control panel. To do so, activate
manual control by pressing the
corresponding button. This prevents
further overrides by the central BMS. You can then
set any other operating mode using the control
panel.
To resume the previous operating mode from the
central BMS, press the manual mode button again.
Manual operation can be set for a limited period.
The manual mode will then automatically be
deactivated after the set delay, and the previous
operating mode will be resumed.
No override option for the room operating
mode
The central BMS can be configured to block
the override function on the room control panel
temporarily or permanently. In this case, manual
control cannot be used, and the control panel
shows only the centrally set operating mode. If a
user attempts to change the operating mode on
the control panel, the active operating mode will
blink briefly.
Lighting
Use this button to switch the room lighting on or off.
This function is only available if the
room management function has been
configured accordingly.
This button can also be used for other
functions instead of or in addition to
switching the lighting on/off, e.g. for switching
certain devices on/off.
Sun protection (e.g. blinds)
Use these buttons to operate the sun protection,
e.g. blinds (by others).
These buttons are available only if this function has
been set for the control panel (configuration of the
room management function).
Open blinds
Close blinds
5 Operation · Room control