Operating manual – Air conditioning unit PT 4500 / 6500 AX

 

ET4500AX

The exhaust tube(s) must carry the air to an area ex-
ternalfrom that being cooled, preferably in the outside 
atmosphere.

  Use the cains provided to support the heat ex- 

  changer. It would be highly angerous to sup- 

  port the heat exchanger by means of the flexi- 

  ble lines alone.

CONDENSATE.
PAC4500AX/PAC6500AX.

In operation, the room unit is constantly condensing 
water vapour out of the atmosphere (reducing relati-
ve humidity). This water has to be drained away. An 
automatic  condensate  pump  is  fitted  inside  all  PA-
C4500AX/PAC6500AX  room  units.  The  flexible  hose 
outlet from the condensate pump runs to the outside, 
inside the flexible sheath and the condensate is de-
posited in the base of the heat exchanger, conside-
rable re-evaporation of this water takes place on the 
warm air stream passing through and around the heat 
exchanger, but please remember that there will also 
be a degree of dripping through the base of the heat 
exchanger.

  Have great regard for this characteristic when  

  positioning the external heat exchanger.

The  flexible  water  pipes  should  be  routed  so  as  to 
avoid  any  possibility  of  kinking  or  unnecessary  re-
strictions to the flow of water inside. Also, remember 
that  plastic  and  rubber  become  much  more  flexible 
when warm and, as a result, much more susceptible 
to distortion. Condensate from the ET4500AX is coll-
ected in an internal tank and emptied by the user. An 
optional pump kit may be fitted to pump liquid via a 
plastic  tube  to  an  external  container  or  the  ground. 
Care needs to be taken in the positoning of the tube.

MACHINE LINK-UP FOR PAC15AX/PAC22AX

Ensure the mains supply lead to the room unit is discon-
nected. A 5 m (extendable to 30 m) line set to connect all 
services between the room unit and the external heat ex-
changer will have been supplied. The water pipe connec-
tions are by means of „quick connect couplers“. These 
are simple ‚push-on“ connectors which, when discon-
nected (after pulling back sprung loaded locking ring), 
re-seal the water system on either side. The complete 
system will have been filled with the necessary amount 
of  water/antifreeze  prior  to  its  arrival  on  site. A  water 
proof 3 pin quick connect electrical coupler (push fit with 
screw lock ring, hand tight only), and condensate drain 
pipe coupler 6 mm clear polythene (push fit), should also 
be connected. Having made the couplings, the system is 
operational immediately.

ROOM  UNIT  WATER  LEVELS  FOR  PAC4500AX/ 

PAC6500AX

The water system in the room unit will be to the cor-
rect level when delivered. However if for some reason 
the level has fallen, antifreeze (33%) and water will have 
to be added. The header tank filler is located to the rear 
of the room unit and can be accessed by removing the 
two screws holding the security plate over the filler tank 
cap, see Fig 2. Ensure the machine is running in cooling 
mode before removing the header tank cap, and as with 
all pressure caps, remove slowly. It is recommended that 
a mixture, by volume, of one part antifreeze to two parts 

DO NOT LET HEAT EXCHANGER

HANG FROM ITS FLEXIBLE LINE

SUPPORT HEAT

EXCHANGER

WEIGHT USING HOOKS

AND CHAINS PROVIDED

OR STAND ON FIRM

GROUND.

Exchanger

3

Summary of Contents for PortaTemp 4500

Page 1: ...62 400 Fax 49 0 24 52 962 200 www trotec de E Mail info trotec de TRO TR BA PT4500 6500AX 04 10 INT PortaTemp 4500 6500 AX Bedienungsanleitung Klimager t A 1 Operating Manual Air conditioning unit B 1...

Page 2: ...ren Das Ger t wurde vor seiner Auslieferung umfangreichen Material Funktions und Qualit tspr fungen unterzogen Trotzdem k nnen von diesem Ger t Gefahren ausgehen wenn es von nicht eingewiesenen Person...

Page 3: ...hat Das Ger t wird von einer standardm igen 13 A Wand dose aus in Betrieb gesetzt Die Gr e eines m gli cherweise benutzten Verl ngerungskabels ist 2 5 mm Minimum bis zu einer H chstl nge von 10 Metern...

Page 4: ...n des W rmeaustauschers hindurch tropfen wird Die flexiblen Wasserrohre sollten so verlegt werden da jede M glichkeit des Knickens oder unn tige Einschr nkungen des inneren Wasserdurchflusses vermiede...

Page 5: ...auf die Position 8 2 Schalten Sie das Klimager t ein die Betriebslampe leuchtet rot 3 W hlen Sie mit dem Betriebsartschalter nur Venti lator Der Ventilator startet jetzt 4 W hlen Sie die Geschwindigke...

Page 6: ...Jahr Ersatzteile sind beim Lieferanten der Einheit er h ltlich 06 ST RUNGEN UND FEHLERBESEITIGUNGEN Arbeiten am Klimager t sollten nur von einem Fachmann vorgenommen werden Problem Kein Luftstrom von...

Page 7: ...verstopft Kondensatschlauch eingefroren Problem Keine K hlung PT 4500 AX Diagnose Gelbe WARN Lampe leuchtet Durchlauf mit flasche montiertem Schalter Abhilfe Darauf achten da Verbindungsschiene an An...

Page 8: ...turer To maintain this status and ensure safe operation you as the user must observe the instruc tions in this user guide This unit MUST be transported and operated in the upright position at all time...

Page 9: ...the angle of air out let to be adjusted vertically and horizontally and in conjunction with the fan speed control switch the air velocity and direction can be carefully set up to obtain maximum cover...

Page 10: ...d via a plastic tube to an external container or the ground Care needs to be taken in the positoning of the tube MACHINE LINK UP FOR PAC15AX PAC22AX Ensure the mains supply lead to the room unit is di...

Page 11: ...lluminate 3 Select Fan Only with the mode switch The fan will start 4 Select Fan Speed with the fan speed switch high or low depending on air velocity required 5 Select Cooling with the mode switch an...

Page 12: ...upplier of the unit itself 06 TROUBLESHOOTING Only a competent electrician should attempt to rectify electrical supply problems Do not remo ve any panels from the machine Problem No air flow from room...

Page 13: ...g water level Kink in condensate tube between room unit and external heat exchanger Leak inside room unit Sump filter inside room unit blocked Condensate tube frozen Problem No cooling ET4500AX Diagno...

Page 14: ...les d clarations et autres documents cet effet sont conserv s au si ge du fabricant Afin de pr server cet tat de l appareil et vous assurer d une utilisation sans danger il vous incombe en tant qu uti...

Page 15: ...Conjointement avec le bouton de contr le de vitesse du ventilateur la vitesse et la direction de l air peuvent tre r gl es soigneusement pour obtenir une couverture maximale de la zone refroidir sans...

Page 16: ...ens t est collect soit dans le r servoir in terne de I appareil vid par I utilisateur ou vacu par une pompe de relevage en option Il est n cessaire de prendre pr caution de la position du tube CONNEXI...

Page 17: ...IGENE La dehumidificateur est fabiqu e avec un circuit de refrigeration qu est un syst me herm tique avec un charge de frigorig ne moins de 6 kg R407c potentiel de rechauffement du globe 1700 04 MISE...

Page 18: ...est situ devant I vaporateur Un second filtre est fix sur le panneau arri re du mod le ET 4500 AX Mod le PAC 6500 AX Soulever la grille d air de retour sur la face avant du climatiseur Fig 4 En repla...

Page 19: ...iseur mo bile est quip de contacteurs HAUTE et BASSE pressi on Ces contacteurs sont r armement manuellement Il suffitd appuyer l g rement sur le bouton qui se trouve derri re l aide d un crayon ou d u...

Page 20: ...ui respecte l environnement et a une influence neutre par rapport l ozone Conform ment aux dispositions l gales et ou locales en vigueur le m lange d huile et de r fri g rant contenu dans l appareil d...

Page 21: ...Mode d emploi Climatiseur PT 4500 6500 AX C 20 8...

Page 22: ......

Page 23: ......

Page 24: ...kalite kontrollerine tabi tutulmu tur Buna ra men e itimsiz personel taraf ndan hatal kullan ld nda veya amac n n d nda kullan ld nda bu cihaz risk olu turabilir Klima cihaz dik konumda ta nmal ve al...

Page 25: ...lmas na dikkat edilmelidir aksi takdirde ciddi karma kl klar meydana gelebilir Evde kullan lan uzatma kablolar n n o u 1 5 mm apa sahiptir Bu uzatma kablolar klima cihaz n al t rmak i in uygun de ildi...

Page 26: ...kullan c taraf ndan bo alt l r S v y bir plastik boru zerinden harici bir hazneye veya ze mine pompalamak i in opsiyonel bir pompa ekipman kurulabilir Boruyu oda nitesi ile harici e anj r aras nda kon...

Page 27: ...a cihaz n al t r n al ma lambas k rm z yanar 3 al ma modu alteri ile sadece fan k sm n se in Fan imdi al maya ba lar 4 Fan h z d mesi ile h z se in stedi iniz gibi y ksek veya d k se ebilirsiniz 5 So...

Page 28: ...cuttur 06 ARIZA G DERME Klima cihaz zerindeki al malar yaln zca uz man bir ki i taraf ndan yap lmal d r Problem Oda nitesinden hava ak m gelmiyor Te his K rm z al ma lambas kapal z m Elektri i a n ve...

Page 29: ...filtre t kanm Yo u mu su hortumu donmu Problem So utma yok PT 4500AX Te his Sar UYARI lambas yan yor Hatal monte edilmi alterli ge i z m Ba lant k za n n ba lant blo una mont e edilmi olmas na dikkat...

Page 30: ......

Page 31: ......

Page 32: ...TROTEC GmbH Co KG Grebbener Stra e 7 D 52525 Heinsberg Tel 49 0 24 52 962 400 Fax 49 0 24 52 962 200 www trotec de E Mail info trotec de...

Reviews: