background image

13

EN

Operating manual – local air conditioner PAC 2010 S

Errors and faults

The device has been checked for proper functioning several
times during production. If malfunctions occur nonetheless,
check the device according to the following list.

The device does not start: 

Check the power connection.

Check the power cable and mains plug for damages.

Check the on-site fusing.

Observe the operating temperature according to the
Technical data chapter.

The condensation tank may be full. Empty the
condensation tank, if need be. The error code 

E4

 must not

be indicated on the segment display.

Wait for 10 minutes before restarting the device. If the
device is not starting, have the electrics checked by a
specialist company or by Trotec.

The device works with reduced or no cooling capacity:

Check whether 

cooling

 mode is selected.

Check the proper fit of the exhaust air hose. In case of
kinks, bends or blockage in the hose, exhaust air cannot
be discharged. Clear the way for the exhaust air.

Check the position of the ventilation flaps. They should be
opened to the maximum.

Check the air filter(s) for dirt. If necessary, clean or replace
the air filter(s).

Check the minimum distance to walls or other objects.
Position the device a little more in the room's centre if
required.

Check whether any windows and/or doors of the room are
open. If so, close them. The window for the exhaust air
hose has to remain open nonetheless.

Check the temperature setting at the device. Reduce the
set temperature if it is higher than the room temperature.

The device is loud or vibrates:

Check whether the device is set up in a stable and upright
position.

Condensate is leaking:

Check the device for leaks.

The compressor does not start:

In 

cooling

 and 

dehumidification

 mode the compressor will

only start at a room temperature of at least 15 °C.

Check whether the overheating protection of the
compressor has tripped. Disconnect the device from the
mains and let it cool down for approx. 10 minutes before
reconnecting it.

Check whether the ambient temperature equals the target
temperature (in 

cooling

 mode) or 24 °C (in 

automatic

operation

). The compressor will not switch on unless the

target temperature is reached.

The compressor may start up with a delay of 3 min, as it is
provided with an internal protection against direct restart.

The device gets very warm, is loud or loses power:

Check the air inlets and air filter for dirt. Remove external
dirt.

From the outside, check the device for dirt (see chapter
Maintenance). If the inside of the device is dirty, have it
cleaned by a specialist company for cooling and 
air-conditioning or by Trotec.

The device does not respond to the infrared remote control:

Check whether the distance between remote control and
device is too large and reduce it if necessary.

Make sure there are no obstacles, such as furniture or
walls, between the device and the remote control. Ensure
visual contact between device and remote control.

Check the charging status of the batteries and change
them if required.

If the batteries have only just been changed, check them
for correct polarity and change them if required.

Notice

Wait for at least 3 minutes after maintenance and
repair work. Only then switch the device back on.

Your device still does not operate correctly after these
checks?

Please contact the customer service. If necessary, bring the
device to a specialist company for cooling and air-conditioning
or to Trotec for repair.

Error codes

The following error messages can be displayed in the segment
display (11):

Error code

Cause

Remedy

E2

Error at the room
temperature sensor

Disconnect the device briefly from the
mains.
Should the error still be displayed after
the restart, please contact the customer
service.

E3

Error at the
temperature sensor of
the evaporator

E5

Error at the
temperature sensor of
the condenser

E4

Condensation tank full Empty the condensation tank (see

chapter Maintenance, Condensate
discharge (manual draining)). Should
the error still be displayed, please
contact the customer service.

Summary of Contents for PAC 2010 S

Page 1: ...TRT BA PAC2010S TC 001 EN PAC 2010 S EN OPERATING MANUAL LOCAL AIR CONDITIONER ...

Page 2: ...t guarantee that they may be used freely and primarily following the spelling of the manufacturer Product names are registered Changes to construction in the interests of constant improvements to the product as well as changes to the shape and colour are reserved The scope of delivery may vary from product images This document was created with all due care Trotec GmbH Co KG accepts no liability wh...

Page 3: ...s plug into a properly secured mains socket Observe the technical data when selecting extensions to the power cable Completely unroll the extension cable Avoid electrical overload Before carrying out maintenance care or repair work on the device remove the mains plug from the mains socket Hold onto the mains plug while doing so Switch the device off and disconnect the power cable from the mains so...

Page 4: ...ct the power cable from the mains socket Hold onto the mains plug while doing so 2 Do not reconnect a defective device to the mains Information about the device Device description The device serves the purpose of cooling the room air It further filters and dehumidifies the air thus creating an agreeable room climate The unit cools the room air by withdrawing warmth The absorbed warmth is emitted t...

Page 5: ...H S l e e p i n g T i m e r M o d e S p e e d PO W ER Sl ee pi ng Ti m er Fa n Co ol i n g Sp ee d De hu mid i f y i n g Au t o ma t i c F C H 1 2 3 4 5 6 5 7 8 9 2 No Designation 1 Control panel 2 Air inlet 3 Handle 4 Wheels 5 Air inlet with air filter 6 Exhaust air hose connection 7 Condensate outlet with rubber stopper 8 Remote control 9 Air outlet with ventilation flaps ...

Page 6: ... contrary might lead to compressor damage and a malfunctioning device If so any warranty claims will be voided Storage Before storing the device proceed as follows Drain the remaining condensate from the device and the condensation drain hose see chapter Maintenance When the device is not being used observe the following storage conditions dry and protected from frost and heat in an upright positi...

Page 7: ... Use cable bridges Make sure that extension cables are completely unrolled Keep air inlets and outlets as well as the exhaust air hose connection free Make sure that no curtains or other objects interfere with the air flow Prior to initial start up insert the batteries in the remote control Inserting the air filter Notice Do not operate the device without an inserted air filter Without an air filt...

Page 8: ... oli ng Sp ee d De hum i d i f y i n g Au t o ma t i c F C H Discharging exhaust air The exhaust air coming from the device contains waste heat from the room to be cooled For this reason it is recommended to discharge the exhaust air to the outside The end of the exhaust air hose can be fed through the open window If required secure the open window with the corresponding means so that the end of t...

Page 9: ...rheat and shut down The dimensions of the exhaust air hose were especially made to fit the device Do not replace or extend the hose for it could cause a malfunction Opening the ventilation flaps 1 Prior to switching the device on open the ventilation flaps at the air outlet Sleeping Tim er Mode Spe ed POW ER Slee ping Time r Fan Cool ing Spee d Dehum idifying Autom atic F C H Connecting the power ...

Page 10: ...ling Dehumidifying dehumidification Automatic automatic operation 13 POWER button Power button Switching the device on and off 14 POWER LED Illuminated when the device is switched on 15 Speed button Setting the fan stage Stage 1 low fan speed Stage 2 high fan speed 16 Mode button Selecting the operating mode automatic operation cooling dehumidification ventilation 17 Decrease value button Reducing...

Page 11: ...ill be illuminated to indicate cooling mode Dehumidification Info Remove the exhaust air hose during dehumidification otherwise the performance will be insufficient In dehumidification mode the humidity level in the room is reduced The temperature cannot be adjusted and the fan runs at speed level 1 1 Press the Mode button 16 until the operating mode LED for Dehumidifying 12 is illuminated ð The S...

Page 12: ...on 12 is illuminated ð The current room temperature is indicated on the segment display 11 2 Press the Speed button 15 to set the desired fan stage ð The Speed LED 10 for the selected fan stage will be illuminated ð The Automatic LED 12 will be illuminated to indicate automatic operation Setting the timer The timer has two modes of operation automatic switch on upon expiry of a preset number of ho...

Page 13: ...to its previous setting Changing the unit C F The temperature in the segment display 11 can be indicated in C or F Please proceed as follows to change the temperature unit 1 Simultaneously press and hold the Increase value 18 and Decrease value 17 buttons for 3 s ð The displayed temperature is converted to the other unit Remote control All settings of the device can also be made using the remote c...

Page 14: ...ice from the mains and let it cool down for approx 10 minutes before reconnecting it Check whether the ambient temperature equals the target temperature in cooling mode or 24 C in automatic operation The compressor will not switch on unless the target temperature is reached The compressor may start up with a delay of 3 min as it is provided with an internal protection against direct restart The de...

Page 15: ...ttachment screws X X Test run X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Empty condensation tank and drain hose Check the air inlets and outlets for dirt and foreign objects and clean if necessary Clean the exterior Visually check the inside of the device for dirt Check the air filter for dirt and foreign objects and cl...

Page 16: ...nings of the device 3 Check the inside of the device for dirt 4 If you see a thick layer of dust have the inside of the device cleaned by a specialist company for cooling and air conditioning or by Trotec 5 Put the air filter back in Cleaning the air filter The air filters have to be cleaned as soon as they are dirty This is brought to light e g by a reduced capacity see chapter Errors and faults ...

Page 17: ... under the condensate outlet S l e ep i n g T i m er M od e S pe ed PO W ER Sl ee pin g Tim er Fa n Co oli ng Sp ee d De hum i d i f y i n g Au t o ma t i c F C H 2 Remove the rubber stopper from the condensate outlet S l e ep i n g Ti m er M od e S pe ed PO W ER Sle ep i n g Tim er Fa n Co oli ng Sp ee d Deh um i d i f y i n g Aut om atic F C H 3 Drain the condensate 4 Reattach the rubber stopper...

Page 18: ... for a considerable time Store the device according to the Storage chapter Technical annex Technical data Model PAC 2010 S Cooling capacity 2 kW Dehumidification performance 1 l h Operating temperature 15 C to 35 C Temperature setting range 15 C to 31 C Max air volume flow 230 m3 h Mains connection 1 N PE 220 V 240 V 50 Hz Nominal current 3 5 A Power input cooling operation 0 8 kW Sound pressure l...

Page 19: ...manual local air conditioner PAC 2010 S Spare parts drawing and list PAC 2010 S Note The position numbers of the spare parts differ from those describing the positions of other parts mentioned in this operating manual ...

Page 20: ...lectric Control Box 31 Cover of Connector 53 Water level switch bracket 10 For rubber 32 Right Cover 54 float switch 11 KSS 33 Condenser 55 Hydro extracting Fan 12 Main Board 34 Evaporator 56 Hydro extracting Motor 13 Motor Capacitor 35 Sense Temperature Bracket 57 Hydro extracting Motorcover 14 Electric Control Box 36 Thermal probe card holder 58 Back Bracket 15 Compressor Capacitor 37 Inner Air ...

Page 21: ... prevent negative effects for the environment and human health caused by the disposal of hazardous substances potentially contained in the equipment You are responsible for deleting any personal data stored on the waste equipment to be disposed of The device is operated with fluorinated greenhouse gas which can be dangerous for the environment and contribute to global warming when emitted to the a...

Page 22: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com ...

Reviews: