TX6351 • TX6352 User Manual
44 P5536.1600 rev B
P5536.1600 rev B 45
4.4.4 Modbus
RS485 Output
• The protocol characteristics required for the Modbus datacomms version
can be setup. Sentro can then be integrated into a wider communication
network or to interface with a PC or SCADA system.
Data Protocol
Modbus
Addresses
1 to 255
Format
Binary
Databits
8
Stopbits
1
Parity
None
Baud Rate
300/600/1200/2400/4800/9600/
14400/19200/28800/38400/57600/115200
TX On
0 to 99 ms
TX Off
0 to 99 ms
Duplex
Half
4.4.5 Module Setup
The functional characteristics of the
Sentro eModule may be setup
to preference.
Change Setpoint 1
Change Setpoint 2
• The Sentro Module provides two adjustable setpoint output signals
• When setpoint 1 (General) is activated, the LED alarm indicators in the
display window fl ash simultaneously at a rate of about once every two
seconds. When setpoint 2 (high) is activated, they fl ash simultaneously at a
rate of about 2 per second
• The Activation mode and operating
level of the setpoints can be setup
to preference.
Checkpoint
• The setpoint output signal data will also be available for transmission
on the RS485 Modbus version of Sentro.
Checkpoint
• The Contact Output version of Sentro 1 is also equipped with two relays
• The Activation will operate in the same way
• The Relay Function mode can also be setup
Section 4.4.3
www.trolex.com
www.trolex.com