background image

8

ELECTRICAL REQUIREMENTS

Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6mm²

38A

10mm²

52A

16mm²

69A

Installed in an 

insulated wall

6mm²

32A

10mm²

43A

16mm²

57A

Clipped direct

or buried in a 
non-insulated 

wall

6mm²

46A

10mm²

63A

16mm²

85A

6mm2

10mm2

16mm2

*The method below may be used by

installers to determine the approximate 

size of the incoming cable.

1.

Measure the width of an individual strand,
and half that measurment to find 

(r)

,

e.g: 

1.34mm ÷ 2 = (r) 0.67mm

2.

Multiply 

(r) x (r)

 x 

3.14,

e.g: 

(r)

 

0.67 x (r)

 

0.67 

3.14 = 1.41mm2

3.

Multiply this by the number of wire strands
(usually 7), e.g: 

1.41mm2 x 7 = 9.87mm2.

4.

The number obtained would suggest

10mm2

 wiring.

*PLEASE NOTE:

 If unsure, consult a qualified Electrician.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

 The switch must be accessible and clearly 

able, but out of reach of a person 

u

xed bath or shower, except for the

cord of a cord operated switch, and should
be placed so that it is not possible to touch
the switch body while standing in a bath or
shower cubicle. It should be readily accessible
to switch off after using the shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the disconnection 

time and thermal constraints which means 
that for any given combination of current 
demand, voltage drop and cable size, there is 
a maximum permissible circuit length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed 
in areas where the ambient temperature 
is above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

  In the majority of installations 

(see 

Table B)

, the cable will unavoidably be 

placed in one or more of the above 
conditions. This being so, it is strongly 
recommended to use a minimum of 10mm 
cabling throughout the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Summary of Contents for T70 GSI

Page 1: ...when not in use This is a safety procedure recommended for all electrical appliances The showerhead and hose supplied with this product are a safety critical part of your shower Failure to use genuin...

Page 2: ...ing other than those specified This appliance is intended to be permanently connected to the water mains and not connected by a hose set A suitable double pole isolation switch for supply disconnectio...

Page 3: ...ulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806 2 2 The supply pipe must be flushed to clear debris before co...

Page 4: ...re setting At different times of the year you may have to adjust the position of the temperature control to maintain your desired temperature setting c The stabiliser valve minimises variations in sho...

Page 5: ...r to the wall 13 15 Plumbing connections 16 Electrical connections 17 Fitting The Cover valve knob positions 18 19 Commissioning procedure 20 Cleaning the filter installers service engineers only 21 F...

Page 6: ...08mm 108mm 308mm ENTRY POINTS DIMENSIONS WATER Left Bottom Back Top Side Right Bottom Back Side CABLE Left Bottom Back Top Side Right Bottom Back Side Back Back Others Others Inlet connection 15mm dia...

Page 7: ...the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main spur socket out...

Page 8: ...ng in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those ro...

Page 9: ...es per minute the inlet of the shower for full performance for 8 5Kw 9 5Kw Minimum running pressure and flow to 150kPa 1 5 bar at 11 litres per minute the inlet of the shower for full performance for...

Page 10: ...he incoming water Economy setting single red circle Economy uses only one of the elements within the heater can NOTE If the stated flow rate required for the unit cannot be met due to low water pressu...

Page 11: ...ure exceeds the showering safety limit the power to the elements will be removed completely although water will continue to flow When the temperature has cooled sufficiently power to the elements will...

Page 12: ...espoke hose retainer it will in most cases meet this requirement If the showerhead can still be placed within a bath basin or shower tray within the 25mm limit then a double check valve or similar MUS...

Page 13: ...the fitting 180 fig 9B Secure with the screw included in the screw pack fig 9C NOTE The Inlet is not fixed during production Deviations from the designated entry points will invalidate product approv...

Page 14: ...ut positions Decide if top or bottom pipe entry is required Once chosen carefully remove the appropriate cut out using a junior hacksaw and file PLEASE NOTE NONE of the cut outs are designed as snap o...

Page 15: ...nto position leaving the base of the screw head protruding 6mm out from the wall Hook the backplate over the top screw and fit the bottom fixing screw into position Do not fully tighten the screws at...

Page 16: ...ss point to the isolator IMPORTANT Before completing the connection of the water supply to the inlet of the shower flush out the pipework to remove all swarf and system debris This can be achieved by...

Page 17: ...IMPORTANT Fully tighten the terminal block screws and make sure that no cable insulation is trapped under the screws Loose connections can result in cable overheating NOTE The supply cable earth cond...

Page 18: ...bottom fig 15 2 With the cover off the shower turn the stabiliser valve spindle fully clockwise until resistance is felt fig 16 4 With the cover off the shower turn the temperature control to the 5 O...

Page 19: ...the OFF position and the temperature control is turned fully clockwise the 5 o clock position Offer the cover to the unit Carefully guide the cover onto the backplate making sure the wires are not tr...

Page 20: ...s to flow from the flexible hose Slowly turn the temperature control fully anti clockwise fig 20 It will take about thirty seconds for a smooth flow of water to be obtained while air and any debris is...

Page 21: ...on SWITCH OFF the electricity and water supply at the mains The inlet filter is situated inside the water inlet fitting fig 21 To gain access to the filter remove the cover and bottom trimplate Unscre...

Page 22: ...ase in ambient water temperature 2 3 1 Readjust flow rate to give increased flow 2 3 2 Select economy power 3 Water temperature cycling hot cool at intervals 3 1 Heater cycling on thermal cut out 3 1...

Page 23: ...ed while commissioning 6 3 1 Fit new PRD Commission unit with showerhead removed 6 4 Water pressure above specified maximum for unit see rating label 6 3 1 Fit pressure reducing valve to inlet and the...

Page 24: ...electric products are labelled accordingly with the crossed out wheeled bin symbol This indicates for disposal purposes at end of life that these products must be taken to recognised collection point...

Page 25: ...TS USED 0 1 2 H O T HOT COLD Turn the main power isolator switch ON Power Knob setting Temperature Knob setting To START the shower turn the power knob from the OFF position to Cold Economy or High 1...

Page 26: ...26...

Page 27: ...27...

Page 28: ...ners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verif...

Reviews: