Triton Madrid II Installation And Operating Instructions Manual Download Page 10

10

3

Continued

SECTION

Table B

Note: 

Cable selection is dependent on 

derating factors

Twin and earth PVC insulated cable

Current carrying capacity

In conduit

trunking

6mm²

38A

10mm²

52A

16mm²

69A

Installed in an 

insulated wall

6mm²

32A

10mm²

43A

16mm²

57A

Clipped direct

or buried in a 
non-insulated 

wall

6mm²

46A

10mm²

63A

16mm²

85A

6mm2

10mm2

16mm2

*The method below may be used by

installers to determine the approximate 

size of the incoming cable.

1.

Measure the width of an individual strand,
and half that measurment to find 

(r)

,

e.g: 

1.34mm ÷ 2 = (r) 0.67mm

2.

Multiply 

(r) x (r)

 x 

3.14,

e.g: 

(r)

 

0.67 x (r)

 

0.67 

3.14 = 1.41mm2

3.

Multiply this by the number of wire strands
(usually 7), e.g: 

1.41mm2 x 7 = 9.87mm2.

4.

The number obtained would suggest

10mm2

 wiring.

*PLEASE NOTE:

 If unsure, consult a qualified Electrician.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

 The switch must be accessible and clearly 

able, but out of reach of a person 

u

xed bath or shower, except for the 

cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily accessible 
to switch off after using the shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B)

.

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the disconnection 

time and thermal constraints which means 
that for any given combination of current 
demand, voltage drop and cable size, there is 
a maximum permissible circuit length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed 
in areas where the ambient temperature 
is above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

  In the majority of installations 

(see 

Table B)

, the cable will unavoidably be 

placed in one or more of the above 
conditions. This being so, it is strongly 
recommended to use a minimum of 10mm 
cabling throughout the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Summary of Contents for Madrid II

Page 1: ...ower IMPORTANT SAFETY ADVICE The shower unit MUST BE switched off at the isolating switch when not in use This is a safety procedure recommended for all electrical appliances The showerhead and hose s...

Page 2: ...ing other than those specified This appliance is intended to be permanently connected to the water mains and not connected by a hose set A suitable double pole isolation switch for supply disconnectio...

Page 3: ...th Water Regulations Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS EN 806 2 2 The supply pipe must be...

Page 4: ...ut out NOTE If ever the water becomes too hot and you cannot obtain cooler water first check that the sprayplate in the showerhead has not become blocked DO NOT place items such as soap or shampoo bot...

Page 5: ...ter supply will satisfy requirements 1 Check that water cable entry points of the unit meet requirements 2 Check that the electric supply will satisfy requirements 3 Siting of the shower 4 Plumbing in...

Page 6: ...tallation 14 Fit to the wall connect shower supplies 14 16 Fitting the cover 17 COMMISSIONING PROCEDURE 18 USER OPERATING INSTRUCTIONS OPERATING FUNCTIONS 19 21 Cleaning the filter installers service...

Page 7: ...1 litres per minute for 10 5kW Maximum static pressure 1000 kPa 10 bar Maximum inlet temperature 28 C Minimum inlet temperature 2 C Inlet connection 15mm diameter Outlet connection BSP male thread MAT...

Page 8: ...ONS WATER Left Side Top Right Bottom Side Back CABLE Left Top Bottom Side back Right SIde Back Back Others Others 210mm 110mm 305mm 2 check list SECTION PLEASE NOTE Deviation from the approved entry p...

Page 9: ...in any doubt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a r...

Page 10: ...g in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outlets in those roo...

Page 11: ...ssible to achieve optimum performance from the unit throughout the year During periods of high ambient temperatures it may be necessary to select the economy power setting to achieve your preferred sh...

Page 12: ...not less than 25mm above the spill over level of the relevant bath shower tray or other fixed appliance If the riser kit is supplied with a soapdish hose retainer or bespoke hose retainer it will in m...

Page 13: ...und the pipework in order to make the nut accessible for future adjustments NOTE An additional stopvalve complying with Water Regulations must be fitted in the mains water supply to the shower as an i...

Page 14: ...ate product approvals The cable entry points are listed on page 8 Seal around rear entry cable to prevent water ingress into the wall FIT TO THE WALL CONNECT THE SHOWER SUPPLIES If a bottom entry has...

Page 15: ...protruding 6mm out from the wall Hook the backplate over the top screw and fit the bottom fixing screw into position but DO NOT fully tighten the screws at this stage The fixing holes are elongated to...

Page 16: ...ve cable to terminal marked L Fig 12 shows a schematic wiring diagram IMPORTANT When connecting the cable fully tighten the terminal block screws and make sure that no cable insulation is trapped unde...

Page 17: ...emperature control knob so that it points to the maximum flow position fig 14 Position the power selector to the STOP position fig 15 Check to ensure that the wiring is not trapped and replace the cov...

Page 18: ...will light 3 Turn the power selector to the COLD position fig 18 and wait until water starts to flow from the flexible hose 4 Slowly rotate the temperature control fully anti clockwise to the maximum...

Page 19: ...the economy setting for using less power during warmer months Temperature adjustment at this setting is via the temperature control Red double symbol is the high setting which allows the highest flow...

Page 20: ...ckwise fig 21 will increase the flow of water through the shower making it cooler To increase the shower temperature Turning the temperature control clockwise fig 22 will decrease the flow of water th...

Page 21: ...the power to the elements will be removed completely although water will continue to flow When the temperature has cooled sufficiently power to the elements will be automatically restored to the sett...

Page 22: ...at the lsolator valve Remove the cover The inlet filter is situated in the inlet pipe which is part of the solenoid valve fig 24 To access the filter remove the trimplate then disconnect and remove th...

Page 23: ...rol 2 1 2 Blocked showerhead clean or replace blocked sprayplate in showerhead 2 2 1 Check if stop valves are fully open Check if a blockage in the inlet filter 2 3 1 Readjust flow rate to give increa...

Page 24: ...perated Have the unit checked by a suitably qualified engineer or contact Customer Service 5 1 1 Wait until the water pressure resumes to normal 6 1 1 Clean or replace blocked sprayplate in showerhead...

Page 25: ...ack scheme DTS registration number 9659 All our electric products are labelled accordingly with the crossed out wheeled bin symbol This indicates for disposal purposes at end of life that these produc...

Page 26: ...USED 2 OF THE ELEMENTS USED 0 1 2 H O T HOT COLD To START the shower turn the knob clockwise A Start Stop position B Cold the shower will be on the Cold setting C Economy the shower will be on the Ec...

Page 27: ...27...

Page 28: ...credit debit card excluding American Express or Diners Card Payment can also be made by pre payment of a pro forma invoice by cheque or postal order Telephone orders are based on information given dur...

Reviews: