background image

Bar Mixer Shower

5

INTRODUCTION

This book contains all the necessary fitting and 
operating instructions for your mixer shower. 
Please read them carefully and read through 
the whole of this book before beginning your 
installation.
The mixer shower installation must be carried out 
by a suitably competent person and in sequence 
of this instruction book.
Care taken during the installation will give a long 
and trouble free life from your mixer shower.

SITE REQUIREMENTS

The installation must be in accordance with 
water supply (water fittings) regulation 1999 
and/or local Bylaws.

Water Pressure Requirements

Running water pressure:

 

Low pressure* 

-  0.1 bar min.

   

  1.0 bar max.

  High pressure 

-  0.5 bar min.

   

  5.0 bar max.

Maximum static water pressure:

 Low & High pressure 

-  10 bar

*This mixer shower is designed for high pressure 
systems found in the UK, but can be installed 
with low pressure gravity water systems with 
reduced flow rates.
For effective operation of the internal seals, the 
maximum static pressure must not be exceeded.

Pressure Reducing Valve

On sites where the running pressure is above 5 
bar, the use of a suitably sized pressure reducing 
valve fitted in the cold mains supply pipework 
can provide nominally equal pressures at the 
mixer shower.

Water Minimum Flow Rate

For best performance within the specified running 
pressure range a minimum flow of 8 litres per 
minute should be available to both inlets.

Water Temperature Requirements

Recommended maximum: 

= 65°C

Minimum hot water temperature:  = 55°C
Maximum cold water temperature:  = 25°C

NOTE:

 Valves operating outside these conditions 

cannot be guaranteed by the Scheme to operate 
as Type 2 valves.
A stored water temperature of 60°C is 
considered sufficient to meet all normal 
requirements and will minimise the effects of 
scale in hard water areas.

Water Temperature Adjustment and 
Thermal Safety

The mixed water temperature can be adjusted 
from cold through to a top limit which must 
be preset during installation with full anti-scald 
protection throughout the range (35°C to 40°C) 
providing the hot water temperature at the inlet 
remains 10°C above the outlet temperature.
Should there be a loss of flow to either incoming 
supply then water from the shower will stop or 
be reduced until both supplies are restored.

SAFETY WARNINGS

a. 

DO NOT

 choose a position where the mixer 

shower could become frozen.

b. 

DO NOT

 connect this mixer shower to any 

form of tap or fitting not recommended by 
the manufacturer.

c. 

DO NOT

 allow the inlet pressure or flow 

rates to operate outside the guidelines laid 
out in Site Requirements.

d.  

DO NOT

 connect the mixer shower to a 

gravity hot supply and a mains cold supply or 
vice versa.

Summary of Contents for DENE HI-FLO

Page 1: ...ER BY TEL 024 7637 8321 INSTALLATION AND OPERATING INSTRUCTIONS Please read this book thoroughly and familiarise yourself with all instructions before commencing installation and keep it for future re...

Page 2: ...OUTLET TEMPERATURES 17 OPERATING THE SHOWER 18 SPARE PARTS 19 TMV2 REQUIREMENTS 12 MONTHLY VERIFICATION 20 APPROVALS 20 FLOW RATES 20 MAINTENANCE 21 FAULT FINDING 22 23 GUARANTEE SERVICE POLICY ETC r...

Page 3: ...Mixer Shower 3 All dimensions listed in this fitting book regarding the product and installation are approximate MAIN COMPONENTS Fig 1 A Thermostatic bar mixer valve B Push fit connector x2 with trims...

Page 4: ...Bar Mixer Shower 4 All dimensions listed in this fitting book regarding the product and installation are approximate 290mm 55mm DIMENSIONS...

Page 5: ...ixer shower Water Minimum Flow Rate For best performance within the specified running pressure range a minimum flow of 8 litres per minute should be available to both inlets Water Temperature Requirem...

Page 6: ...lushed through before fitting Commercial Applications It is recommended that for all commercial applications easily accessible in line filters are used to aid maintenance Hard Water Areas a If it is i...

Page 7: ...essures as shown please refer to the pump installation guide to establish the minimum head requirements for automatic operation of the pump Hot water cylinder Cold supply Hot supply Alternative supply...

Page 8: ...ems with no cold water take off after the appliance reducing valve it will be necessary to fit an additional drop tight pressure reducing valve when the mains pressure is over 5 bar The drop tight pre...

Page 9: ...ing An expansion vessel MUST be fitted and regularly maintained to ensure the unit is not damaged by excess pressures This may already be installed externally or internally within the thermal store ch...

Page 10: ...r panel SITING OF THE SHOWER ACCESSORIES Refer to fig 7 for correct siting of the shower The mixer shower should be positioned as detailed with all controls within comfortable reach of the user The ac...

Page 11: ...imum b DO NOT choose a position where the mixer shower could become frozen c DO NOT connect to any form of tap or fitting not recommended by the manufacturer d Conveniently situated service valves in...

Page 12: ...earance should be provided behind the finished wall at the point at which the pipework exits the wall to allow the pipe to be moved in and out of the wall by a minimum distance of 4mm This distance sh...

Page 13: ...quired and chase out additional areas of the wall to allow for the incoming pipework Make sure that enough solid structure of wall remains around the chasing to accommodate the mounting plate wall plu...

Page 14: ...of any debris or damage Clean the surface if necessary IMPORTANT Press a push fit connector onto each pipe until the pipe is pushed past the O ring and reaches the stop within the connector This can...

Page 15: ...to secure the connector fig 17 Using a suitable sealant seal the join between the mounting plate and the wall or tiles to prevent water entering the wall fig 17 Wipe away any excess sealant which may...

Page 16: ...ide button Allow the shower to run at this maximum temperature setting until the water temperature has stabilised Rotate the temperature control until your desired maximum showering temperature is rea...

Page 17: ...must never exceed 46 C at terminal fitting The British Burns Association recommends 37 to 37 5 C as a comfortable bathing temperature for children In premises covered by the Care Standards Act 2000 th...

Page 18: ...water stops flowing To adjust the water temperature rotate the temperature control right hand side clockwise for cooler or anti clockwise for hotter fig 24 To overcome the maximum temperature stop de...

Page 19: ...0310 Flow regulator 4 0 L M 22011740 Flow regulator 5 0 L M 22011750 Flow regulator 6 0 L M 22011760 Flow regulator 7 0 L M 22011610 Flow regulator 8 0 L M 22011280 Flow regulator 12 0 L M 22013060 Re...

Page 20: ...king correctly and no further service work is required If there is a residual flow during the commissioning or the annual check this is acceptable providing the temperature of the water seeping from t...

Page 21: ...once every 12 months a Initially check the filters for debris once every three months and clean if necessary b Perform a thermal shut off test every three months and check the maximum temperature set...

Page 22: ...blocked or restricted 2 6 Flow regulator not fitted HP systems only 3 1 Flow regulators not fitted 1 1 1 Refer to the Commissioning section 1 2 1 Reposition temperature control knob 1 3 1 Reposition...

Page 23: ...nlet filters Clean if necessary 4 3 1 Turn off the shower and consult a suitably competent plumber 4 4 1 Clean showerhead 4 5 1 Reduce the simultaneous demand 4 5 2 Make sure stop service valves are f...

Page 24: ...ent of a pro forma invoice by cheque or postal order Telephone orders are based on information given during the call Before contacting Triton please verify your requirements using the Information cont...

Reviews: