background image

5

7. Installation

7.2.3 Equipment Connections

Never work on power equipment while it is energized. De-energize equipment and lock off all power to the equipment before working 
inside.

The top and bottom panels of the equipment are the recommended designated areas for landing conduit to the equipment. All conduits 

must be located to avoid interference with structural members and live bus. A set of drawings for the specific configuration of the equipment 
is included inside the equipment. Reference the equipment drawings in 

Section 10 Reference Materials

.

All conductors are to be sized for 167°F (75°C) ampacity. When cable is used with temperature ratings above 167°F/75°C, it shall be 
sized based on the ampacity of cable rated 167°F (75°C).
The equipment must be grounded with the appropriately sized conductor in compliance with Article 250 of the National Electrical 

Code (NEC). The ground conductor should be terminated to the main ground bus bar inside the equipment.

Remove the equipment covers as needed to access the input and output connection points. Where cables enter or exit the equipment or 
pass through any metal which has magnetic properties, they shall be arranged so all phase and neutral conductors are grouped together 
and pass through the same opening in compliance with Article 300.20 of the National Electrical Code (NEC). When pulling cable into the 

equipment, take care not to damage any of the internal components and control wiring. Position the cables inside of the equipment so they 

are not subject to physical damage and are not forced permanently against the edges of any metal parts. If any cables are in contact with 
sharp edges, place suitable protective material between the cable and the metal edge to protect the cable insulation.
Using the appropriate tools, strip a length of insulation from the end of the cable sufficient to fit into the full length of the mechanical lug 
for the designated connection point. If using aluminum conductors, apply an appropriate antioxidant compound to the bare aluminum. 

Insert the bare conductor into the lug so the bare conductor fills the full length of the mechanical lug body. Tighten the set screw on the 

mechanical lug and torque to the values indicated on the Torque Values Label located on the equipment.
Reference the Equipment Schematic Drawing for information on the required connections between the Maintenance Bypass Panel, the UPS 

and the critical load.

7.2.4 Pre-Energizing Inspection

Inspection and maintenance should only be performed on equipment that has been de-energized and electrically isolated so that no 

accidental contact can be made with energized parts.

The top and bottom panels of the equipment are the recommended designated areas for landing conduit to the equipment. All conduits 

must be located to avoid interference with structural members and live bus. A set of drawings for the specific configuration of the equipment 

is included inside the equipment. Reference the equipment drawings in 

Section 10 Reference Materials

.

Before energizing the equipment, it must be thoroughly inspected.
1.  Remove any foreign materials from inside of the equipment including tools, scraps of wire or other debris.
2.  Visually inspect the equipment for any damage that may have occurred during the installation process. Be sure to inspect all insulators, 

busbars and other conductors. Do not energize if any damage is found!

3.  Verify cable phase orientation at all connection points.
4.  Verify all field cable connections are properly torqued.
5.  Manually operate all circuit breakers to verify proper operation.
6.  Verify the circuit breaker trip unit adjustments are set per the end user requirements.
7.  Verify equipment ground connections are properly terminated.
8.  Review the Kirk Key interlock operating sequence and confirm the Kirk Key interlocks are performing properly.
9.  Verify all covers are installed.

7.2.5 Energizing

Hazardous voltages in electrical equipment can cause severe injury or death!
Only qualified persons should attempt to install or service this equipment. A qualified person is one who has skills and knowledge 
related to the construction and operation of electrical equipment and installations and has received safety training on the hazards 

involved.
Ensure maximum continuous loads do not exceed 80% of the overcurrent protective device (circuit breaker and fuses) ratings at 
nominal input voltage of 208V/120V AC employed in other than motor circuits, except for those circuits employing circuit breakers 

marked as suitable for continuous operation at 100% of their ratings.

Extreme hazards can exist when energizing electrical equipment. Take all precautions necessary to protect people and property when 
energizing this equipment. Before energizing the equipment, open/turn off all circuit breakers and verify the Kirk Key interlocks are in the 
correct state to allow for proper startup. Refer to the UPS manual for proper startup procedures.

Summary of Contents for SU140KMBPK

Page 1: ...Concealed Damage 3 4 4 Return of Damaged Goods 3 5 System Overview 3 6 System Specifications 3 6 1 Electrical 3 6 2 Environmental 3 6 3 General 4 7 Installation 4 7 1 Preparation 4 7 1 1 Equipment Inspection 4 7 1 2 Necessary Equipment and Tools 4 7 1 3 Installation Safety Precautions 4 7 1 4 Storage 4 7 2 Installation Steps 4 7 2 1 Equipment Location 4 7 2 2 Equipment Mounting 4 7 2 3 Equipment C...

Page 2: ...ization by Tripp Lite could result in equipment damage personal injury or death Never work on power equipment while it is energized De energize equipment and lock off all power to the equipment before working inside Inspection and maintenance should only be performed on equipment that has been de energized and electrically isolated so that no accidental contact can be made with energized parts SAV...

Page 3: ...pplite com support to file a claim Please contact your shipping company for all shipping damage Tripp Lite is not responsible for any shipping damage 4 4 Return of Damaged Goods Should equipment be damaged and require return to Tripp Lite for repair a representative will provide instructions along with an RMA number to expedite the return An RMA number must be obtained before returning equipment t...

Page 4: ...e are any questions concerning this manual or any of the installation or maintenance procedures and or requirements please contact a Tripp Lite representative before proceeding 7 2 1 Equipment Location This equipment is intended to be installed in a restricted access location The permanent location of the equipment must be on a smooth and solid wall surface Do not locate the equipment against a no...

Page 5: ...een the Maintenance Bypass Panel the UPS and the critical load 7 2 4 Pre Energizing Inspection Inspection and maintenance should only be performed on equipment that has been de energized and electrically isolated so that no accidental contact can be made with energized parts The top and bottom panels of the equipment are the recommended designated areas for landing conduit to the equipment All con...

Page 6: ... 4 Insert the key in SW3 and retract the bolt 5 Turn OFF SW3 breaker 6 Turn OFF SW1 7 The UPS is now ready for routine maintenance 8 If further maintenance requires a total shutdown of the UPS and isolation from the input the SW1 breaker must be opened turned off and the battery supply to the UPS must be disconnected Refer to your UPS manual for proper shutdown procedures Return to Normal Operatio...

Page 7: ...normally prevent electrical damage except at the point where the short circuit occurred High mechanical stress developed by short circuit currents may cause damage to conductors insulation or other components After a fault thorough inspection of the entire system must be made to verify that there is no damage Circuit breakers which performed the short circuit interruption must be inspected for pos...

Page 8: ...pment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended Any action for breach relating to the sale of a Tripp Lite product must be commenced within one year after the cause of action has been accrued THIS LIMITED WARRANTY IS IN LIEU OF ANY OTHER WARRANTY EXPRESS OR IMPLIED AND ALL SUCH WARRANTIES ...

Page 9: ...ción de Mercancía Dañada 11 5 Visión General del Sistema 11 6 Especificaciones del Sistema 11 6 1 Eléctricas 11 6 2 Ambientales 11 6 3 General 12 7 Instalación 12 7 1 Preparación 12 7 1 1 Inspección del Equipo 12 7 1 2 Equipo y Herramientas Necesarias 12 7 1 3 Precauciones de Seguridad en la Instalación 12 7 1 4 Almacenamiento 12 7 2 Pasos para la Instalación 12 7 2 1 Ubicación del Equipo 12 7 2 2...

Page 10: ...n el equipo sin la autorización de Tripp Lite podrían generar daños en el equipo lesiones físicas o muerte Nunca trabaje con equipos eléctricos mientras están conectados a la alimentación Desconecte el equipo y bloquee toda la alimentación antes de trabajar en el interior La inspección y el mantenimiento deberán realizarse solamente en equipos que hayan sido desconectados de la alimentación eléctr...

Page 11: ...ripplite com support para presentar un reclamo Póngase en contacto con su compañía de envío en relación con todos los daños del embarque Tripp Lite no es responsable por daños durante el embarque 4 4 Devolución de Mercancía Dañada Si el equipo se daña y necesita devolverlo a Tripp Lite para su reparación un representante le dará instrucciones junto con un número de RMA para agilizar la devolución ...

Page 12: ...el equipo Si tiene preguntas con respecto a este manual o cualquiera de los procedimientos de instalación o mantenimiento o de los requisitos póngase en contacto con un representante de Tripp Lite antes de continuar 7 2 1 Ubicación del Equipo Este equipo está diseñado para ser instalado en un lugar de acceso restringido La ubicación permanente de los equipos debe ser sobre una superficie lisa y só...

Page 13: ... realizarse solamente en equipos que hayan sido desconectados de la alimentación eléctrica y aislados eléctricamente de modo que no haya contacto accidental con partes energizadas Los paneles superior e inferior del equipo son las áreas designadas recomendadas para colocar conductos al equipo Todos los conductos deben ubicarse para evitar interferencias con elementos estructurales y buses activos ...

Page 14: ...llave 4 Introduzca la llave en SW3 y retraiga el perno 5 Apague el breaker SW3 6 Apague el SW1 7 El UPS está ahora listo para mantenimiento de rutina 8 Si se requiere mantenimiento adicional se debe apagar por completo el UPS y aislar desde la entrada se debe abrir apagar el breaker SW1 y se debe desconectar el suministro de la batería al UPS Consulte el manual del UPS para conocer los procedimien...

Page 15: ...produjo el cortocircuito La alta tensión mecánica desarrollada por las corrientes de los cortocircuitos puede provocar daños en los conductores el aislamiento u otros componentes Después de una falla debe inspeccionarse todo el sistema para verificar que no haya daño alguno Se deben inspeccionar los breakers que provocaron la interrupción por cortocircuito para detectar posibles daños No desarme e...

Page 16: ...uipo de soporte de vida o afectar significativamente su seguridad o efectividad Cualquier acción por incumplimiento en relación con la venta de un producto de Tripp Lite debe iniciarse dentro del plazo de un año posterior a la causa de acción acumulada ESTA GARANTÍA LIMITADA REEMPLAZA CUALQUIER OTRA GARANTÍA EXPRESA O IMPLÍCITA Y TODAS ESAS GARANTÍAS QUEDAN EXCLUIDAS INCLUIDAS ENTRE OTRAS CUALQUIE...

Page 17: ...etour de marchandises endommagées 19 5 Aperçu du système 19 6 Caractéristiques techniques du système 19 6 1 Électricité 19 6 2 Conditions environnementales 19 6 3 Généralités 20 7 Installation 20 7 1 Préparation 20 7 1 1 Inspection de l équipement 20 7 1 2 Équipement et outils nécessaires 20 7 1 3 Mesures de sécurité pour l installation 20 7 1 4 Entreposage 20 7 2 Étapes de l installation 20 7 2 1...

Page 18: ... l équipement sans l autorisation de Tripp Lite pourrait causer des dommages à l équipement des lésions corporelles ou la mort Ne jamais effectuer des travaux sur de l équipement électrique qui se trouve sous tension Mettre l équipement hors tension et verrouiller toutes les sources d alimentation de l équipement avant de travailler à l intérieur N effectuer l inspection et l entretien que sur de ...

Page 19: ...our tout dommage survenu pendant l expédition Tripp Lite n est responsable d aucun dommage survenu pendant l expédition 4 4 Retour de marchandises endommagées Si l équipement est endommagé et doit être retourné à Tripp Lite pour être réparé un représentant fournira des instructions de même qu un numéro d autorisation de retour de matériel RMA pour expédier le retour Un numéro RMA doit être obtenu ...

Page 20: ...retien contacter un représentant de Tripp Lite avant de procéder 7 2 1 Emplacement du matériel Cet équipement est destiné à être installé dans un endroit à accès restreint L emplacement permanent de l équipement doit être sur une surface murale lisse et solide Ne pas placer l équipement contre un plafond non ignifuge Laisser un espace de 0 9 m 3 pi entre le plafond et l équipement à moins qu un éc...

Page 21: ... et isolé électriquement de manière à éviter tout contact accidentel avec des parties sous tension Les panneaux supérieur et inférieur de l équipement sont les endroits désignés recommandés pour acheminer le conduit vers l équipement Tous les conduits doivent être situés de manière à éviter toute interférence avec les membres structurels et le bus sous tension Un ensemble de dessins pour la config...

Page 22: ...rétracter le boulon 5 Mettre le disjoncteur SW3 en position OFF arrêt 6 Mettre SW1 en position OFF arrêt 7 L onduleur est maintenant prêt pour l entretien de routine 8 Si un entretien plus approfondi nécessite un arrêt total de l onduleur et une isolation de l entrée le disjoncteur SW1 doit être ouvert fermé et l alimentation de la batterie vers l onduleur doit être déconnectée Consulter le manuel...

Page 23: ...t circuit s est produit De fortes contraintes mécaniques créées par des courants de court circuit peuvent causer des dommages aux conducteurs à l isolation et aux autres composants Après une défaillance effectuer une inspection approfondie de l ensemble du système afin de vérifier l absence de tout dommage Les disjoncteurs qui ont interrompu le court circuit doivent être inspectés pour la présence...

Page 24: ...majeure à sa sécurité ou à son efficacité Toute action pour une violation relative à la vente d un produit Tripp Lite doit être engagée dans l année après la constatation de la cause de l action LA PRÉSENTE GARANTIE LIMITÉE REMPLACE TOUTE AUTRE GARANTIE EXPRESSE OU TACITE ET TOUTES CES GARANTIES SONT EXCLUES Y COMPRIS SANS S Y LIMITER TOUTE GARANTIE TACITE DE QUALITÉ MARCHANDE OU D ADAPTATION À UN...

Reviews: