10
Installation
4-2
Default Shutdown Setting (UPS Only):
During a loss of utility power, the
Accessory is configured to shut down the UPS system 2 minutes after a low
battery signal is received from the UPS. This allows the UPS to provide the
maximum available runtime to connected equipment. If you want to change the
default setting, follow these instructions:
1. From the initial PowerAlert Status page, click the
Settings
button
A
at the top
of the screen, then click the Events button
B
that appears at the left side of
the screen.
2. From the
Event Settings
page, confirm that the
Low Battery Shutdown
C
box
is checked and then click the Details Tab
D
, or double-click the checked box
to access the Setting Details page.
3. From the Details page
E
, choose your preferred settings from the Settings
drop down menu
F
and click the
Save Changes
button
G
.
Note for Network Management System Users Only: Two MIB files - Tripplite.mib
and RFC1628.mib - must be loaded on each Network Management Station that
will monitor the UPS system or Inverter/Charger via SNMP. The files are provided
on the CD-ROM included in the product package.