background image

Built-in UPS output
receptacles

Hardwire

Output receptacle
backplate options

Optional backplates SUPDM12 (for 208v nominal), SUPDM14 (for 240v nominal), SUPDM16 (for 208v nominal) add
low and high voltage outlets, plus L6-30P input cord

Output circuit breaker

40A double-pole

Output AC waveform
(AC mode)

Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current
(at maximum load)

30A

Nominal Input
Voltage(s) Supported

208V AC; 240V AC

UPS input
connection type

Hardwire

UPS input
connection
description

3 wire single phase input (L1, L2, G); optional, country-specific backplates SUPDM12 (for 208v nominal), SUPDM14
(for 240v nominal), SUPDM16 (for 208v nominal) add low and high voltage outlets, plus L6-30P input cord

Input circuit breaker

40A double-pole

Recommended
Electrical Service

30A 208V or 240V

BATTERY

Full load runtime
(minutes)

8 min. (4200w)

Half load runtime
(minutes)

20 min. (2100w)

Expandable battery
runtime

Supports extended runtime with optional external battery packs

External battery pack
compatibility

BP240V10RT3U

BP240V557C-1PH

BP240V787C-1PH

BP240V1037C-1PH

BP240V1407C-1PH

DC system voltage
(VDC)

240

Battery recharge rate
(included batteries)

Less than 6 hours from 10% to 80%

Battery replacement
description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Online, double-conversion power conditioning

Overvoltage
correction

2% output voltage regulation during overvoltages to 276

Undervoltage
correction

2% output voltage regulation during undervoltages to 156

LEDS ALARMS & SWITCHES

LED Indicators

6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options

Summary of Contents for SmartOnline SU6000RT3U

Page 1: ...continuous sine wave output with zero transfer time offers guaranteed uptime and compatibility with all equipment types Hardwire input and output connections support a variety of permanent or PDU styl...

Page 2: ...es Supports detailed monitoring of equipment load levels self test data and utility power conditions via built in RS 232 interfaces Optional SNMPWEBCARD offers communications and control via secure re...

Page 3: ...Recommended Electrical Service 30A 208V or 240V BATTERY Full load runtime minutes 8 min 4200w Half load runtime minutes 20 min 2100w Expandable battery runtime Supports extended runtime with optional...

Page 4: ...utput includes load isolation transfomer protection PHYSICAL Installation form factors supported with included accessories 4 post 19 inch rackmount mounting rail kit included Tower Included mounting a...

Page 5: ...x 25 Included battery pack dimensions height x width x depth cm 13 3 x 44 4 x 63 5 Included battery pack weight lbs 136 5 Included battery pack weight kg 62 Shipping weight lbs 380 Shipping weight kg...

Page 6: ...cy bypass operation with a maximum output voltage variation of 10 Double conversion mode is automatically restored as mains voltage varies beyond 10 with less than 1 millisecond transfer time between...

Page 7: ...protection for data and communication lines 1 BP240V557C 1PH External battery pack for use with select Tripp Lite UPS Systems 1 BP240V787C 1PH External battery pack for use with select Tripp Lite UPS...

Reviews: