![Tripp Lite SmartOnline SU6000RT3U Features And Specifications Download Page 2](http://html1.mh-extra.com/html/tripp-lite/smartonline-su6000rt3u/smartonline-su6000rt3u_features-and-specifications_1167893002.webp)
Double-conversion operation converts raw input from AC to DC, then re-synthesizes output power back to perfect sine wave AC with
enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS
types
Accepts input voltages between 156 and 276, regulating output within 2% of selectable 208/240 and 120V AC output
Standard included 3U battery pack provides 20 minutes runtime at half load (3000VA) and 8 minutes at full load (6000VA)
Expandable runtime is supported with optional BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH;
BP240V1407C-1PH external battery packs
Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs
PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as
UPS batteries become depleted
Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA
(Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250
SNMP-enabled UPS, PDU and other networking devices
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 interfaces
Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces
Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification
Supports Emergency Power Off (EPO) via built-in interface
Included rail kit supports 9U 19 inch rackmount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks
Front panel LED's and LCD readout with scroll controls and supports visual monitoring of all major UPS functions and advanced UPS
settings for nominal voltage selection, economy mode, and other operational parameters
LED / LCD display panel rotates for viewing in rackmount or tower configurations
Network-grade AC surge and noise suppression
External battery packs are field replaceable and hot swappable
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
6000
Output kVA capacity
(kVA)
6
Output Watt Capacity
(watts)
4200
Output kW capacity
4.2
Output power factor
0.7
Crest Factor
3:1
Nominal Output
Voltage(s) Supported
120V; 208V; 240V
Frequency
compatibility
50 / 60 Hz
Frequency
compatibility details
Output frequency matches input nominal on startup
Output voltage
regulation (line mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%