NO BP*
SCROLL SELECT
Continued on page 22.
NO
SCROLL SELECT
21
Operation
To Change This
Setting:
Press “SELECT” (^)
Press “SELECT” (^) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are:
To Advance to
the Next Screen:
Press SCROLL (
v
)
13
The FACTORY DEFAULT selection screen will appear.
FACTORY DEFAULT gives users a quick and easy way to return the UPS to its original factory
configuration. When selecting YES to FACTORY DEFAULT in the LCD Set-Up screens, the
UPS will immediately revert to the original shipping configuration and set of presets.
Running a FACTORY DEFAULT will restore these factory settings:
OUTPUT VOLTAGE = 120
OUTPUT FREQUENCY = 60Hz
BYPASS RANGE = WIDE
OVERLOAD ALARM = 105%
SHUTDOWN AFTER = DISABLE
BATTERY SAVE = DISABLE
STANDBY MODE = NO OUTPUT
FREQ CONVERTER = DISABLE
ECONOMY MODE = DISABLE
COLD START = ENABLE
BATTERY TEST = MONTHLY
EXTERNAL BATT = NO BP
FACTORY DEFAULT = YES
AUDIBLE ALARM = ENABLE
ALARM HISTORY = ALL MESSAGES CLEARED
INFORMATION = NO CHANGE
To Change This
Setting:
Press “SELECT” (^)
Press “SELECT” (^) to SET this value.
Press “SCROLL” (
v
) to advance to the next option.
Available values are: NO, YES
Scroll through available values and press SELECT
(^) to SET.
Factory default = None
To Advance to
the Next Screen:
Press SCROLL (
v
)
Note: The UPS must be
in Standby Mode to
change this setting.
UPS MODEL
Factory
Default
Conigure via LCD
Coniguration via EXTERNAL BATTERY
CONFIGURATION TOOL software
Battery pack
option 1
Battery pack
option 2
Battery pack option 3
(BP TOOL on LCD display)
SU3000RTXLCD2U
NO BP
BP72V15-2U BP72V28RT-3U
BP72V28RT3U (for more than 1)
Scroll through available values and press SELECT (^) to SET.
Factory default = NO BP
If you’re planning on using your UPS with the additional supported battery pack option
listed above as battery pack option 3, EXTERNAL BATTERY CONFIGURATION TOOL software
is required. After the EXTERNAL BATTERY CONFIGURATION TOOL software is used, the UPS
will display the resulting configuration as “BP TOOL” on the LCD screen. BP TOOL is present
as an LCD viewable option, but is itself not selectable (if BP TOOL selection is attempted,
the screen will report “READ ONLY. SELECT BY BP TOOL” to confirm the selection has not
been accepted). EXTERNAL BATTERY CONFIGURATION TOOL software is a Windows only
application and requires a serial cable connection to the UPS in order to run.
Visit http://www.tripplite.com/bpconfig to download the software.
Battery Pack Models That Require Use of EXTERNAL BATTERY CONFIGURATION TOOL
Software:
UPS MODEL
BATTERY PACK MODEL
SU3000RTXLCD2U
BP72V28RT3U (for more than 1)
13-07-015-9332C3.indb 21