background image

The SU1500XLCD includes 2 load banks of 3 outlets each that are individually controllable via a software interface for remote reboot of locked-up

equipment or load shedding to maximize battery backup time for mission-critical equipment.

Reliable, Expandable Battery Backup

UPS battery backup keeps connected equipment operational through short power failures, and provides time to save data and perform an orderly

system shutdown in case of a prolonged blackout. The SU1500XLCD features a large internal battery set that provides 14 minutes of battery support

for a half load (675 watts) and 4.5 minutes for a full load (1350 watts). During normal operation, incoming utility power keeps the UPS battery fully

charged so that backup power will always be available if needed. For mission-critical applications demanding continuous uptime, the fully scalable

SU1500XLCD can provide expandable runtime with optional external battery packs (Tripp Lite model BP48V24-2U or BP48V60RT-3U), sold

separately.

High Power Factor and Highly Efficient Operation Reduces BTU Output

The SU1500XLCD features a high 0.9 power factor and an optional, highly efficient economy mode setting that can significantly reduce a facility’s

energy costs. In economy mode, the UPS operates with 97% efficiency, minimizing heat output, reducing cooling requirements and consuming less

electricity.

AC Line and Tel/Ethernet Surge Suppression

A sudden power surge or spike can damage or destroy electronic components and wipe out irreplaceable data. The SU1500XLCD features a

570-joule surge suppression rating to protect connected components and data from the harmful effects of power surges. One set of tel/Ethernet

(RJ45) jacks provides surge protection for a standard phone or network connection (cable not included).

EMI/RFI Line Noise Filtering

Various electrical and radio sources can cause disruptive interference on the AC line. This line noise is a common cause of incremental hardware

damage, data corruption and audio/video performance problems. The SU1500XLCD incorporates technology that filters out disruptive line noise,

preventing it from affecting your equipment.

LCD Screen and Audible Alarm

The SU1500XLCD features a front-panel LCD screen that enables IT personnel to monitor line power, on-line mode, bypass mode, on-battery,

overload, battery low, replace battery and fault status information. It is supplemented by an audible alarm that signals UPS startup, power failure, low

battery, overload, UPS fault and remote shutdown conditions.

USB/DB9 Ports, SNMP Capability and Included PowerAlert Software

The SU1500XLCD features an HID-enabled USB port and a DB9 port (cables included). Used with Tripp Lite’s included PowerAlert software, these

communication ports provide comprehensive network power monitoring and control. Capabilities include UPS and line power status messaging (on

battery, low-battery, power restored, AC line voltage, DC battery voltage and remaining battery capacity), timed inverter shutoff after unattended

shutdown, and UPS output power control for delayed or immediate reboot of connected devices. The SU1500XLCD also accepts an optional

SNMPWEBCARD accessory that enables the UPS to operate as a managed device on the network.

Emergency Power Off (EPO) Capability

The SU1500XLCD features an EPO interface port that supports emergency shutoff in large facilities (cable included).

Peace of Mind

The SU1500XLCD comes with $250,000 Ultimate Lifetime Insurance coverage for connected equipment and a 2-year warranty.

Specifications

OUTPUT

Output Volt Amp
Capacity (VA)

1500

Output kVA
capacity (kVA)

1.5

Summary of Contents for SmartOnline SU1500XLCD

Page 1: ...meters and line power status Included PowerAlert power management software supports an unlimited number of network UPS systems The SU1500XLCD also accepts an optional SNMPWEBCARD accessory that enables the UPS to operate as a managed device on the network It comes backed by a 2 year warranty and 250 000 of Ultimate Lifetime Insurance Package Includes SU1500XLCD SmartOnline Tower UPS System PowerAl...

Page 2: ... provides surge protection for a standard phone or network connection cable not included EMI RFI Line Noise Filtering Various electrical and radio sources can cause disruptive interference on the AC line This line noise is a common cause of incremental hardware damage data corruption and audio video performance problems The SU1500XLCD incorporates technology that filters out disruptive line noise ...

Page 3: ...ut frequency on startup Output matches input frequency when 5Hz of nominal Output is regulated to 0 05Hz when input frequency exceeds 5Hz of nominal UPS switches to battery mode when input frequency is below 40Hz or above 70Hz FREQUENCY REGULATION CONVERSION MODE Output is regulated to 0 05Hz of selected output frequency when input is 40 to 70Hz UPS switches to battery mode when input frequency is...

Page 4: ...teries Less than 3 hours from 10 to 90 Replacement battery cartridge internal UPS battery replacement RBC48 SUTWR Battery Access Battery access door Battery replacement description Hot swappable user replaceable batteries VOLTAGE REGULATION Voltage regulation description Online double conversion power conditioning Overvoltage correction 2 output voltage regulation during overvoltages to 150 Underv...

Page 5: ...ise suppression Yes PHYSICAL Installation form factors supported with included accessories Tower Primary form factor Tower UPS Power Module dimensions in primary form factor height x width x depth inches 10 2 x 9 x 19 5 UPS Power Module dimensions in primary form factor height x width x depth cm 25 9 x 22 9 x 49 5 UPS Power Module weight lbs 52 3 UPS Power Module weight kg 23 7 UPS Shipping dimens...

Page 6: ...ommunications cable USB and DB9 cabling included WatchDog compatibility Supports Watchdog application OS and hard reboot restart options for remote applications LINE BATTERY TRANSFER Transfer time Zero transfer time 0 ms in online double conversion and frequency regulation conversion modes Low voltage transfer to battery power setpoint 55V 33 load 70V 70 load 100V 100 load High voltage transfer to...

Page 7: ...uires ENVIROSENSE 1 PDUB15 Single Phase Hot Swap PDU 15A 120V 2U Horizontal Rackmount 8 NEMA 5 15R outlets set of 2 NEMA 5 15P input plugs 1 PDUMH15AT Single Phase Auto Transfer Switch Metered PDU 15A 120V 1U Horizontal Rackmount 8 NEMA 5 15R outlets 2 NEMA 5 15P inputs 1 PDUMNV15 Single Phase Monitored PDU 15A 120V 0U Vertical Rackmount 16 NEMA 5 15R outlets NEMA 5 15P input plug 1 PDUMV15NET Sin...

Reviews: