background image

Built-in UPS output
receptacles

Hardwire

Output AC waveform
(AC mode)

Sine wave

Output AC waveform
(battery mode)

Pure Sine wave

INPUT

Rated input current (at
maximum load)

50A

Nominal Input
Voltage(s) Supported

208V AC / 120V AC (4 wire split single phase); 240V AC /120V AC (4 wire split single phase)

UPS input connection
type

Hardwire

UPS input connection
description

4 wire split-phase input (L1, L2, N, G)

Recommended
Electrical Service

50A 208/240-120 Split Phase

Phase

Single-Phase

BATTERY

Full load runtime
(minutes)

7 min. (8400w)

Half load runtime
(minutes)

20 min. (2400w)

Expandable battery
runtime

Supports extended runtime with optional external battery packs

External battery pack
compatibility

BP192V18-4U

BP192V557C-16K

BP192V787C-16K

BP192V1037C-16K

BP192V1407C-16K

DC system voltage
(VDC)

192

Battery recharge rate
(included batteries)

Less than 6 hours from 10% to 80%

Battery replacement
description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation
description

Online, double-conversion power conditioning

Overvoltage correction

3% output voltage regulation during overvoltages to 140 (measured L1-N : L2-N)

Undervoltage
correction

3% output voltage regulation during undervoltages to 65 (measured L1-N : L2-N)

LEDS ALARMS & SWITCHES

LED Indicators

6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options

Alarms

Unique audible alarms for all major UPS, environmental and power conditions (see manual)

Alarm cancel operation

Alarm cancel switch