background image

3

2 – Important Safety Instructions 

continued

•  Even after the AC supply circuit is disconnected, there is a risk of dangerous electrical shock when the external battery pack is connected to the 

UPS system. Disconnect the external battery pack before servicing the UPS system.

•  Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life 

support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a 
flammable anesthetic mixture with air, oxygen or nitrous oxide.

•  Output Protection: An easily accessible disconnect switch must be provided for the AC output circuit (L21-N22). To reduce the risk of fire, 

connect the output only to a circuit provided with 45 amperes maximum branch circuit overcurrent protection in accordance with the National 
Electrical Code (NEC), ANSI/NFPA 70. 

•  Input Protection: To reduce the risk of fire, connect the input only to a circuit provided with 65 amperes maximum branch circuit overcurrent 

protection in accordance with the National Electrical Code (NEC), ANSI/NFPA 70.

Wiring Warnings

•  Refer to all applicable local, state and national codes (including NEC) for appropriate cable size and ratings.
•  The UPS system contains hazardous high voltages that have the potential to cause personal injury or death from electric shock.
•  The UPS system has its own energy source. The output terminals may be live even when the UPS system is not connected to a utility power source.
•  The UPS system must be suitably grounded according to all applicable electrical wiring regulations.
•  De-energize all input and output power sources before installing cables or making electrical connections.
•  Use flexible cable of sufficient length to permit UPS system servicing.
•  Use 75° C minimum copper wire for AC input/output connections.
•  Tighten all connections with a torque of at least 2.60 N•m (23 in•lb).
•  Confirm that all cables are marked correctly according to their purpose, phase, polarity and diameter.
•  Observe proper polarity by connecting negative to negative and positive to positive. Observe proper phase by connecting R to R, S to S, T to T 

and N to N. Failure to observe proper phase or polarity will damage the UPS system and create a risk of personal injury and property damage.

•  Wiring should be performed by trained, qualified electricians only.

Battery Warnings

•  Allow batteries to charge uninterrupted for 12 hours after installation.
•  There are no user-serviceable parts inside the UPS system. Battery service or replacement must be performed or supervised by qualified 

service personnel familiar with batteries and the required precautions.

•  When replacing batteries, replace only with the same quantity, type and capacity.
•  Do not connect or disconnect batteries when the UPS system is operating from the battery supply. Disconnect the charging source prior to 

connection or disconnecting battery terminals.

•  Batteries present a risk of electrical shock from high short-circuit current. Observe these precautions when working with batteries: Remove 

watches, rings or other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not place tools or metal parts on 
batteries. Disconnect the charging source prior to connecting or disconnecting battery terminals. Do not short or bridge the battery terminals 
with any object.

•  Hazardous voltage may exist between the battery terminals and ground – test before touching.
•  Turn off and unplug the UPS system before performing battery replacement.
•  Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic
•  Do not dispose of batteries in a fire. They may explode.
•  The batteries are recyclable. Refer to local codes for disposal requirements. Do not dispose of batteries except through approved channels in 

accordance with all applicable local, state and national regulations.

•  Tripp Lite offers a complete line of UPS system Replacement Battery Cartridges (R.B.C.). Contact Tripp Lite to determine the specific 

replacement battery for the UPS system.

•  If the UPS system is unused or placed in storage for any length of time, follow the recharging instructions in 

Section 11 – Storage and Service

 

to avoid a permanent loss of battery capacity. Failure to recharge the batteries periodically may cause permanent battery damage. Battery 
damage caused by failure to follow the recharging instructions will not be covered under warranty.

Note on Labeling

These symbols may appear on the product label:

V~ 

AC Voltage

V    DC Voltage
Ø 

Phase

Refer to the product label for model numbers, voltage ratings and other important information.

  

Ground

Battery Positive

Battery Negative

Summary of Contents for SmartOnline SU10KRT1X

Page 1: ...Mounting 5 4 1 Unpacking 5 4 2 Placement 6 4 3 Mounting Rack 6 4 4 Mounting Tower 7 5 Wiring 8 5 1 Wiring Preparation 8 5 2 Terminal Block Diagram 8 5 3 Electrical and Cable Data 8 5 4 AC Input Output...

Page 2: ...tilation openings of the UPS system or otherwise impede the airflow from the front to the rear of the UPS system Do not place any object on the UPS system especially containers of liquid Spilling liqu...

Page 3: ...damage the UPS system and create a risk of personal injury and property damage Wiring should be performed by trained qualified electricians only Battery Warnings Allow batteries to charge uninterrupt...

Page 4: ...Note Remove the network card in order to use the RS 232 port B Settings Switch for Parallel Redundancy Operation C CAN Bus Connection Ports for Parallel Redundancy Operation D Cooling Fans E External...

Page 5: ...unit Inspect the unit carefully prior to installation If anything appears to be damaged contact Tripp Lite for service Retain the packing materials for future use Packing List 1 UPS Power Module 1 Ext...

Page 6: ...tact the manufacturer of the rack or rack enclosure for a solution 4 Post Mounting Procedure Note The mounting procedure is identical for the external battery pack and the UPS power module Mount the e...

Page 7: ...ition Pull the panel out slightly rotate it and push it back into place Tower Mounting Procedure 1 Use M4 flat head screws S2 to attach covers A5 to four of the tower feet A4 2 Use M3 flat head screws...

Page 8: ...y pack Mark all cables according to their correct purpose polarity phase and diameter Review the diagram in Section 5 2 to familiarize yourself with the terminal block Consult the table in Section 5 3...

Page 9: ...eves through the knockouts in the terminal block cover A2 Each input output wire should terminate with a ring terminal 3 Connect the ring terminal for each input output cable to the appropriate input...

Page 10: ...system 1 Switch the external battery pack s DC breaker to the OFF position 2 Remove the terminal covers from the UPS power module s external battery pack DC cable connector and the external battery pa...

Page 11: ...in economy mode 6 Fault LED This red LED illuminates when UPS system experiences a fault or other abnormal condition If the condition persists after restarting the UPS system refer to Section 9 Troubl...

Page 12: ...f temperature voltage amperage level percentage and frequency Indicates the category being measured line load battery EPO Emergency Power Off Code Description Er05 Battery Weak or Dead Er06 Output Sho...

Page 13: ...and the battery charger begins to charge the external battery pack 8 Press the ON button for approximately 3 seconds then release it The UPS will beep twice and the LCD screen will change from B to C...

Page 14: ...elapsed you will need to repeat the previous step 5 The UPS system will run a self test and display H again Battery mode startup is successful and connected equipment will operate until the battery i...

Page 15: ...tely three seconds until the buzzer sounds twice then release the buttons Except for buzzer Q1 Q2 and self test R1 R2 all other default settings may now be changed by pressing the Previous Change Sett...

Page 16: ...upply circuit is securely grounded Start up Procedure 1 Position the UPS systems as specified above 2 Connect the parallel communication cables C1 C2 to the Ring loop at a maximum length of 7 m Secure...

Page 17: ...rting the EPO terminals activates the EPO emergency power off function which provides emergency shutdown of the UPS system Note The network card must be removed in order to use the UPS system s RS 232...

Page 18: ...t LED Er16 Er27 All parallel UPS parameters except ID number must be same Adjust the parameters Fault LED Er21 Reconnect the RJ45 cable or set a UPS with ID 1 Fault LED Other Error Code Have a qualifi...

Page 19: ...tility power source Next disconnect all equipment The UPS system must be stored in a clean secure environment with a temperature less than 40 C and a relative humidity less than 90 non condensing Note...

Page 20: ...he batteries are designed for hot swap replacement i e replacement while the UPS system is in ON mode but some qualified service personnel may wish to put the UPS system in OFF mode and disconnect equ...

Page 21: ...cific legal rights and you may have other rights which vary from jurisdiction to jurisdiction Tripp Lite 1111 W 35th Street Chicago IL 60609 USA WARNING The individual user should take care to determi...

Reviews: