18
LCD Display Navigation
(continued)
“Other Information” Sub-Menu
This sub-menu allows managers to view a variety of additional UPS
System information.
UPS
Status
Code
Note: a UPS Status Code is displayed in the upper-right corner of the
screen in the following display. Use the chart below to determine what
the UPS Status Code indicates.
Displayed
UPS Status
0
Bypass Output Inhibited
2
Load on Reserve
10
Rectifier AC Soft-Start
18
Performing Inverter Test
20
Load on Inverter
22
Load on Inverter at Backup Mode
24
Low Battery
26
Low Battery Shutdown
28
Short-Circuit Shutdown
30, 58
Manual Bypass On
32
Parallel Communication Cable Abnormal
34
Inverter Fault Shutdown
36
Inverter Overload Shutdown
38
Overload Under Parallel (N-1)
40, 42
Inverter Output Voltage Abnormal
44
Inverter IGBT Driver Protection
(Output Voltage Abnormal)
46
EPO Event Shutdown
50
DC BUS Overvoltage Protection Shutdown
52, 54, 56
Inverter Fuse Open (R/S/T Phase)
60, 62, 64
Inverter Over-temperature Shutdown (R/S/T Phase)
66
Output Transformer Over-temperature Shutdown
68, 70
Auxiliary Power Abnormal (PCB-C/A)
72
Feedback Protection
LCD Navigation Key
Action
Buttons to Push
Scroll Up Through Menu
Scroll Down Through Menu
Enter or Select a Menu Choice
Exit Current Menu and Return to Previous Menu
and
simultaneously
Code