12
Wiring the UPS
WARNING! All electrical wiring must be performed by a qualified
electrician or trained professional. Make sure line power is OFF.
Switch OFF UPS input and output breakers before making any
electrical connections. Adhere to all electrical codes when wiring the
input connections.
AC Input and Output Wiring
AC IN
L N
L N
AC OUT
AC input and output wiring requires 12 AWG gauge wiring with a torque specification of
13 in•lb (1.47 N•m).
• Install the input and output hardwire terminal strain reliefs prior to securing AC
wiring to the UPS.
• Connect 120V AC line power input to the L, N and G “AC IN” terminals of the UPS.
• Connect 120V AC UPS output from the L, N and G “AC OUT” terminals of the UPS to
the connected equipment.