Installation
2-2
Input Power Cord Connection (Select
Models with Unattached Power Cords
Only):
Insert the IEC 60320 C19
(PDUMH20HVNET) or IEC 60320 C13
(PDUMH15HVNET) connector
A
of the
input power cord into the IEC 60320
C20 (PDUMH20HVNET) or IEC 60320
C14 (PDUMH15HVNET) inlet
B
of the
PDU. Connect the other end of the input
power cord
C
to a compatible source of
AC power, such as a UPS system, PDU
or utility outlet. The PDU should be
provided with over-current protection:
PDUMH20HVNET should be provided
with a maximum 20A branch-rated over-
current protection device;
PDUMH15HVNET should be provided
with a maximum 15A branch-rated over-
current protection device.
Note:
The AC power source should not share
a circuit with a heavy electrical load (such as
an air conditioner or refrigerator).
2-3
Connect Input Power Cord
(PDUMH15NET and PDUMH20NET):
Connect the input plug
A
to a
compatible source of AC power, such as
a UPS system, PDU or utility outlet. The
PDU should be provided with over-
current protection: PDUMH15NET with a
maximum 15A branch-rated protection
device. PDUMH20NET with a maximum
20A branch-rated protection device.
2-4
Equipment Power Cord Connection:
Insert the IEC 60320 C14 connectors
A
of the equipment power cords into the
IEC 60320 C13 output receptacles
B
of
the PDU (PDUMH15HVNET and
PDUMH20HVNET). Insert power cords
into the NEMA 5-15R output
receptacles
B
(PDUMH15NET) or NEMA
5-15/20R output receptacles
B
(PDUMH20NET). The LED
C
near each
output receptacle illuminates when the
receptacle is ready to distribute live AC
power. The digital load meter
D
will
display the total connected equipment
load in amps.
Networking the PDU
For network configuration instructions, please refer to the WEBCARDLX owner’s manual (PN
93358E) included with this product.