LifeSafety Power, Inc. | PH 888.577.2898 | [email protected]

P03-004 Rev A06

A8 / A8P Installation Manual

Содержание FlexPower A8

Страница 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com P03 004 Rev A06 A8 A8P Installation Manual ...

Страница 2: ...ent discussed within this manual has been tested to the following standards UL294 UL2044 CSA C22 2 107 1 Mounting the A8 Power Distribution Accessory Mounting of the board to an enclosure is via the four snap in standoffs supplied 1 Locate the appropriate mounting holes in the enclosure and snap the standoffs into the holes 2 Align the board mount ing holes with the standoffs be sure the PC board ...

Страница 3: ...e their BR fastons wired together for proper operation except for between the DC and AC sections of an FPX hybrid system 4 Output Selection Jumpers JP1 JP8 These jumpers select which voltage buss input is select ed for the output Jumper numbers correspond with the zone number e g JP1 is the jumper for OUT1 Possible settings are as follows Position 2 Left B2 Buss Position 1 Right B1 Buss Removed Di...

Страница 4: ...er set in Position 2 will have a continuous 28VAC output This application shows dual A8 s for sixteen zone distribution The B1 input is connected to the blue lead 24VAC output of the FPA dual tapped transformer B2 input is connected to the orange lead of the FPA transformer for 28VAC output Any zone output with its jumper set in Position 1 will have a continuous 24VAC output Any zone output with i...

Страница 5: ...5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 B1 B2 BR B1 B2 BR B1 B2 BR B1 B2 BR OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 JP1 2 1 JP2 2 1 JP3 2 1 JP4 2 1 JP5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 A8 Application Examples Typical 300VA 16 outputs with zone select 24 28V AC power ...

Страница 6: ...AGE will occur JP1 2 1 JP2 2 1 JP3 2 1 JP4 2 1 JP5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 i OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 JP1 2 1 JP2 2 1 JP3 2 1 JP4 2 1 JP5 2 1 JP6 2 1 JP7 2 1 JP8 2 1 B1 B2 BR B1 B2 BR B1 B2 BR B1 B2 BR A8 Application Examples Typical 600VA 16 outputs with zone select 24 28V AC power ...

Страница 7: ...unication board used in FPO systems NL4 A11 NetLink network communication board used in FPO systems NLR A11 002 NetLink network communication kit remote reset used in FPA systems NS2 A11 003 Reset module board for use with NL1 RB2 A25 001 2A Relay 12VDC or 24VDC input range DP DT RB5 A25 002 5A Relay 12VDC or 24VDC input range DP DT RB8 A25 003 8A Relay 12VDC or 24VDC input range DP DT Hardware Or...

Страница 8: ... its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notice In addition LifeSafety Power reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification LifeSafety Power FlexPow...