8
Storage
To avoid battery drain, all connected equipment should be turned off and disconnected from
the UPS. Press the power button
and disconnect the unit from AC power. Your UPS will be
completely turned off (deactivated), and will be ready for storage. If you plan on storing your
UPS for an extended period, fully recharge the UPS batteries every three months. Plug the
UPS into a live AC outlet, turn it on by pressing the power button
and allow the batteries
to recharge for 4 to 6 hours. If you leave your UPS batteries discharged for a long period of
time, they will suffer a permanent loss of capacity.
Storage and Service
Battery Replacement
Under normal conditions, the original battery in your UPS will last several years. Battery
replacement should only be performed by qualified personnel. Refer to “Battery Warnings” in
the Important Safety Instructions section for more information.
Models AVRT450U and BC600TU require one 12V DC, 7AH replacement battery.
Models AVRT650U and SMART550USB2 require one 12V DC, 9AH replacement battery.
For further information about replacement compatibility and ordering, visit
www.tripplite.com/products/battery-finder.
Battery replacement must be done using the same battery type and
quantity: 12V DC sealed lead-acid, 6-cell and in compliance with UL 1989.
CAUTION: Risk of energy hazard. Before replacing batteries, remove
conductive jewelry such as chains, wristwatches and rings. High energy
passing through conductive materials may cause severe burns.