6
Basic Operation
LED Indicators
Description
Fault
LED (Red)
Battery
LED (Amber)
Online
LED (Green)
Alarm
Line Mode
Off
Off
On
Off
Battery Mode
Off
Flashes Every
10 Seconds
Off
Off
Battery Low
On
Flashes Every
1 Second
Off
Sounds Every
1 Second
Line Mode
Overload Alert *
Off
Off
On
Sounds Every
0.5 Second
Battery Mode
Overload Alert **
Off
Flashes Every
1 Second
Off
Sounds Every
0.5 Second
Line Mode
Overload Fault *
On
Off
Off
Sounds
Continuously
Battery Mode
Overload Fault **
Off
Off
Off
Off
Replace Battery
Flashes Every
Minute
Off
On
Sounds Every
Minute
Fault Condition
On
Off
Off
Sounds
Continuously
*Line Mode Overload Alert Condition - 110%±10%, goes to fault after 5 minutes; Overload Fault
Condition - 120%±10%, goes to fault immediately.
**Battery Mode Overload Alert Condition - 110%±10%, shuts down in 5 seconds; Battery Mode Overload
Fault Condition - 120%±10%, shuts down immediately.
18-11-060-933853.indb 6
11/20/2018 8:42:21 AM