4. Control Panel and LCD Operations
Table 4.6: Setup-General Setting List
Setting Item
Sub Item
Explanation
Model Name
--
Set UPS Name (xxxxxxxxxx).
The max. length is 10 characters.
Language
--
English only
TIME
Adjust Time
Set current date and time.
(yyyy / mm / dd hour : min : sec)
MUST be set after UPS installation
System Installed Date
Set system installed date
(yyyy / mm / dd)
2018/1/1 (Default)
MUST be set after UPS installation
System Last Maintain Date
Set system latest maintenance date
(yyyy / mm / dd)
MUST be set after UPS installation
Maintainer/Administrator Only
Battery Installed Date
Set battery installed date
(yyyy / mm / dd)
MUST be set after UPS installation
Battery Last Maintain Date
Set battery latest maintenance date
(yyyy / mm / dd)
MUST be set after UPS installation
Baud Rate
--
Set SNMP Port (COM Port0) Baud Rate
• 2400 (Default)
• 4800
• 9600
Set RS-232 Port (COM Port1) Baud Rate
• 2400 (Default)
• 4800
• 9600
Audible Alarm
--
Set Audible Alarm
• Disable
• Enable (Default)
Factory Reset
--
Restore to factory default setting
Refer to
Table 4.7
EEPROM Reset
--
Restore EEPROM to default setting
Refer to
Table 4.7
EPO Function
--
Set EPO active status
• Normal Close Active (Default)
• Normal Open Active
Password
--
Set New Password.
0000 (Default)
Save Setting
--
Save all settings to EEPROM.
Use this feature to save the changed setting(s). Must be performed when
any changes are made to the settings.
Startup Screen
--
Set up initial screen. (xxxxxxxxxxxx).
The max. length is 12 characters.