Measuring Power Tools and Small Appliances 

  

This section applies to any device under test that uses a line cord. For 

double insulated power tools, the meter’s leads should be connected to 

the device’s housing (chuck, blade, etc.) and the lines of the power 

cord. 

 
 
 
 
 
 

 

Testing AC Motors 

 

Disconnect the motor from the line by disconnecting the wires from the motor terminals or opening 

the mains switch. 

If the mains switch is opened, and the motor also has a motor-starter, then the starter must be held 

in the ON position. With the mains switch opened, the measured resistance will include the 

resistance of the motor wire and all other components between the motor and the main switch. If a 

weakness is indicated, the motor and other components should be checked individually. If the motor 

is disconnected at the motor terminals, connect one meter lead to the grounded motor housing and 

the other lead to one of the motor leads. Refer to diagram at below. 

  

Motor 

Starter 

Mains 

Line 

Switch 

 

 

 

GND 

 

Notes: 

 

 

 

 

 

 

1.  The STARTER must be in the ON position during the 

 

 
 
 
 
 

 

Testing DC Motors 

 

1.  Disconnect the motor from the line. 

 

2.  To test the brush rigging, field coils and armature, connect one meter lead to the grounded 

motor housing and the other lead to the brush on the commutator. 

 

3.  If the resistance measurement indicates a weakness, raise the brushes off of the commutator 

and separately test the armature, field coils and brush rigging (one at a time). Leave one lead 

connected to the grounded motor housing while testing the motor components. This also 

applies to DC Generators. 

 
 
 
 

 

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for MG430

Page 1: ...measurements Circuit connections must not be touched during a test Use extreme caution when working near bare conductors and bus bars Accidental contact with conductors could result in electrical shoc...

Page 2: ...eplaced before using the meter Failure to do so could result in damage to equipment and electrical shock Insulation Resistance Measurements Megohmmeter Tests Warning Do not perform Insulation Resistan...

Page 3: ...he voltage value on the LCD 5 Resistance Measurement WARNING Do not run this test unless ACV 0 Do not use this mode to check diodes 1 Set the Rotary switch to the 200k position 2 Connect the red test...

Page 4: ...is indicated the motor and other components should be checked individually If the motor is disconnected at the motor terminals connect one meter lead to the grounded motor housing and the other lead t...

Page 5: ...0 200M 500V 0 1M 3 5d 500V 10 0 0 1000M 1000VDC 1M 3 5d 1000V 10 0 1000 2000M 1000VDC 1M 5 5d 1000V 10 0 Range Test Current Short Circuit Current 200M 250V 250k load 200M 500V 1mA 500k load 1mA 0 100...

Page 6: ...ut Impedance Overload Protection 1000VDC 1V 0 8 3d 10M 1000Vrms RESISTANCE Range Resolution Accuracy Max Open Circuit Overload Voltage Protection 200 0 1 1 2d 4 5V 250Vrms 200k 0 1k 1 2d 3V 250Vrms ww...

Page 7: ...ymbol displayed when battery voltage is low Environmental Installation category III Pollution Degree 2 Altitude up to 2000 meters Indoor use only Power source Six 6 1 5 AA batteries Fuse 250mA 600V ce...

Page 8: ...l purchaser of these goods for use Triplett warrants to the original purchaser for use that the products sold by it will be free from defects in workmanship and material for a period of 1 one year fro...

Reviews: