Maintenance

The following symptoms indicate that the spray nozzle requires cleaning or replacement.  For best performance, nozzle 

should be replaced in lieu of cleaning.

• Larger spray pattern

• Non symmetrical spray pattern

• Constant water stream

• Not spraying water

To Clean the Spray Nozzle

1.  Turn the power to the furnace OFF.

2.  Turn the humidistat to the lowest position.

3.  Turn off the water supply at the saddle valve.

4.  Remove the screw securing the cover of the humidifier to the housing.

5.  Remove the cover assembly from the humidifier by tilting outward.

6.  Be careful not to kink the water supply line or cause undue strain on the wiring.

7.  Hold the nozzle adapter with a 3/4” wrench and using a 5/8” wrench, turn the spray nozzle counter clockwise and 

remove the nozzle.

8.  Remove the screen from the nozzle by turning it counter clockwise.

9.  Holding the spray nozzle with the 5/8” wrench, insert a 5/32” allen wrench into the set screw and turn it counter 

clockwise and remove the components. 

10. Rinse and clean all parts. Suggested cleaners include 50/50 solution of white vinegar and water or liquid humidifier 

cleaner.

11.  Using a razor blade, carefully clean the (4) slots on the director (see diagram below).

12. Reassemble the nozzle assembly, paying careful attention to the diagram below for the correct replacement of 

parts.

13. After completing the assembly, operate the unit to be sure it is functioning properly.

NOTE:

 It is recommened that the nozzle be replaced annually to avoid mineral build-up and possible clogging.  Upon 

replacing the nozzle, check thoroughly for leaks.

Nozzle Body

O-ring

Strainer Screen

Director

Slots

Summary of Contents for Mister-MINI

Page 1: ...Tr i o n w w w t r i o n i a q c o m READ AND SAVE THESE INSTRUCTIONS Mister MINI Duct Mounted Atomizing Humidifer...

Page 2: ...ocation Selection 6 Mounting 7 Wiring 8 Plumbing 9 Start up Operation 10 Maintenance To Clean and Inspect 11 To Check for Leaks 11 To Clean Spray Nozzle 12 To Clean Solenoid Valve 13 Unit Diagram and...

Page 3: ...hold more moisture By using a humidifier a source of water is provided to satisfy this increased moisture holding capability rather than having it drawn from our body surface and the surrounding furn...

Page 4: ...rriers tight storm windows and doors and a dampered fireplace Air exchange rate of 5 changes per hour An Average Home is insulated and has a dampered fire place but there are no vapor barriers storm d...

Page 5: ...nozzles at varying water pressures The capacity listed on the nozzle is for 2 fuel oil at 100 psi and should not be considered relative to the water capacity of this humidifier Nozzle Pressure PSI No...

Page 6: ...control switches air conditioning or heat coils or walls of the duct The humidifier should be mounted so that the furnace air carries the mist away from the humidifier temperature switch The directio...

Page 7: ...ystems 3 Tape the template included inside the carton in place on the duct 4 Drill the 4 1 8 diameter holes as indicated These are used to secure the unit to the duct 5 Neatly cut out the 3 1 8 x 3 1...

Page 8: ...difier whenever the circulating air blower is in operation Read the instructions in the furnace installation manual carefully before attempting installation or operation of the humidi fier Failure to...

Page 9: ...at may get stuck in the solenoid valve seat or clog the spray nozzle When finished turn the saddle valve off again 4 Cut off any excess length of copper water tubing and connect it to the humidifier u...

Page 10: ...dity for automatic humidity control during the heating season a lower setting may be used to control condensation on single pane windows Due to the operation cycle of the furnace and humidifier it may...

Page 11: ...aminants can find its way into the air handling system and ultimately the humidifier The humidifier is not the source of these impurities To clean and inspect the unit 1 Turn the power to the furnace...

Page 12: ...nozzle adapter with a 3 4 wrench and using a 5 8 wrench turn the spray nozzle counter clockwise and remove the nozzle 8 Remove the screen from the nozzle by turning it counter clockwise 9 Holding the...

Page 13: ...se undue strain on the wiring 7 Remove the solenoid valve assembly from the cover using a Phillips head screwdriver 8 Using a 3 4 wrench remove the brass nozzle adapter from the OUT port of the valve...

Page 14: ...TAT 1 3 266121 001 G 109C SOLENOID VALVE ASSEMBLY 1 4 266122 001 WIRE ASSEMBLY 2 5 EST 1434 SCREW SST MACH M4 x 6MM 2 6 142983 003 CHRISTMAS TREE CLIP 1 7 AH 25 NPT x COMPRESSION FITTING 1 8 12006 01...

Page 15: ...l customerservice trioniaq com Humidifiers which have been installed or become part of real estate cannot be returned Trion will receive freight prepaid only removable parts or components of such defe...

Page 16: ...Trion 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Trion 2015 All Rights Reserved Form No 265240 001 Rev 02 15...

Reviews: