background image

Mister-

MINI

®

 Humidifier

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

9

www.trioniaq.com

Installation

Plumbing - USE COPPER WATER TUBING ONLY: 

1.  Install a saddle valve (not included) to a source of water per the instructions printed on the saddle valve package.

2.  Fasten a copper water line (not included) of sufficient length to reach from the humidifier to the saddle valve.

3.  With the end of the copper water line pointing into a bucket or pan, turn on the saddle valve to wash the tubing of any debris 

that may get stuck in the solenoid valve seat or clog the spray nozzle.  When finished, turn the saddle valve off again.

4.  Cut off any excess length of copper water tubing and connect it to the humidifier using the nut and ferrule provided on 

the humidifier.  Slide the nut onto the copper water tubing and then slide the ferrule onto the water tubing.  Assemble 

the nut to the compression fitting on the humidifier by turning it clockwise 1 ¼ to 1 ½ turns past hand-tight to seal.

5.  Turn the saddle valve back on and check the humidifier and tubing for leaks.

1/4” 

Compression 

Fitting

Copper 

Tubing

Compression 

Nut

Optional Wiring

Electrical Connections (24 VAC)

Brass 

Ferrule

Nut & Ferrule 

supplied with saddle 

valve (not included 

with humidifier)

Summary of Contents for Mister-MINI

Page 1: ...Tr i o n w w w t r i o n i a q c o m READ AND SAVE THESE INSTRUCTIONS Mister MINI Duct Mounted Atomizing Humidifer...

Page 2: ...ocation Selection 6 Mounting 7 Wiring 8 Plumbing 9 Start up Operation 10 Maintenance To Clean and Inspect 11 To Check for Leaks 11 To Clean Spray Nozzle 12 To Clean Solenoid Valve 13 Unit Diagram and...

Page 3: ...hold more moisture By using a humidifier a source of water is provided to satisfy this increased moisture holding capability rather than having it drawn from our body surface and the surrounding furn...

Page 4: ...rriers tight storm windows and doors and a dampered fireplace Air exchange rate of 5 changes per hour An Average Home is insulated and has a dampered fire place but there are no vapor barriers storm d...

Page 5: ...nozzles at varying water pressures The capacity listed on the nozzle is for 2 fuel oil at 100 psi and should not be considered relative to the water capacity of this humidifier Nozzle Pressure PSI No...

Page 6: ...control switches air conditioning or heat coils or walls of the duct The humidifier should be mounted so that the furnace air carries the mist away from the humidifier temperature switch The directio...

Page 7: ...ystems 3 Tape the template included inside the carton in place on the duct 4 Drill the 4 1 8 diameter holes as indicated These are used to secure the unit to the duct 5 Neatly cut out the 3 1 8 x 3 1...

Page 8: ...difier whenever the circulating air blower is in operation Read the instructions in the furnace installation manual carefully before attempting installation or operation of the humidi fier Failure to...

Page 9: ...at may get stuck in the solenoid valve seat or clog the spray nozzle When finished turn the saddle valve off again 4 Cut off any excess length of copper water tubing and connect it to the humidifier u...

Page 10: ...dity for automatic humidity control during the heating season a lower setting may be used to control condensation on single pane windows Due to the operation cycle of the furnace and humidifier it may...

Page 11: ...aminants can find its way into the air handling system and ultimately the humidifier The humidifier is not the source of these impurities To clean and inspect the unit 1 Turn the power to the furnace...

Page 12: ...nozzle adapter with a 3 4 wrench and using a 5 8 wrench turn the spray nozzle counter clockwise and remove the nozzle 8 Remove the screen from the nozzle by turning it counter clockwise 9 Holding the...

Page 13: ...se undue strain on the wiring 7 Remove the solenoid valve assembly from the cover using a Phillips head screwdriver 8 Using a 3 4 wrench remove the brass nozzle adapter from the OUT port of the valve...

Page 14: ...TAT 1 3 266121 001 G 109C SOLENOID VALVE ASSEMBLY 1 4 266122 001 WIRE ASSEMBLY 2 5 EST 1434 SCREW SST MACH M4 x 6MM 2 6 142983 003 CHRISTMAS TREE CLIP 1 7 AH 25 NPT x COMPRESSION FITTING 1 8 12006 01...

Page 15: ...l customerservice trioniaq com Humidifiers which have been installed or become part of real estate cannot be returned Trion will receive freight prepaid only removable parts or components of such defe...

Page 16: ...Trion 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Trion 2015 All Rights Reserved Form No 265240 001 Rev 02 15...

Reviews: