SECTION III INSTALLATION INSTRUCTIONS
Mounting
The cabinet is designed to safely contain the working components
of the Herrtronic 6000 series humidifier and dissipate heat to
protect the electronics. Locate humidifier in a manner to allow
routine inspection and any necessary maintenance. DO NOT
install the unit above false ceilings or around valuable property,
where a malfunction could cause damage. Correct positioning of
the humidifier is important to allow for proper operation and easy
maintenance. Minimum clearance around the cabinet should be
maintained as follows:
Minimum Clearances
Around Cabinet
Left
6”
Right
12”
Top
18”
Bottom
12”
Remove foam packing from top of cylinder. Four lag bolts, (2)
5/16” and (2) 1/4”, are supplied with the 6000 unit. Install the
top two lag bolts (5/16”) according to the dimensions in Figure
2. Hang the unit on the wall, and then install the bottom two lag
bolts (1/4”) and secure all four bolts. Be sure the unit is level and
mounted directly to the wall to wood studs at least 2” thick (or
equivalent). Operating weight: 35 lbs.
Figure 2
WARNING!
Do not mount any controls inside the unit or tap power
from any location in the unit, except as stated in these
instructions. Do not place objects near the cabinet. Do
not attach to dry wall without studs. At least one 5/16”
and one 1/4” lag bolt must be located on a stud.
Engineering and Application
The Herrtronic 6000 Series Steam Humidifiers can be applied in
a variety of applications. The simplest application is to utilize the
model with the built-in blower package. The steam generated by
the unit is distributed into the conditioned space by the built-in
blower package (Figure 1).
Figure 1
Allowable Operating Conditions:
Ambient Temperature: 40°F (4°C) to 120°F (50°C)
Ambient Relative Humidity: 0% to 90% (non-condensing)
Line Voltage: -15% to +10% of Nominal
Frequency: 50/60 HZ.
Water Supply Pressure: 20 psi – 100 psi.
Note: Duct liner may be used
with a maximum
thickness of 1".
5 FEET MINIMUM
5 FEET MINIMUM
18 INCHES
MINIMUM
5 FEET MINIMUM
9"
1"
4 1/4"
16 1/2"
1/2"
1 1/2"
5/16 x 5/8 DIA.
KEYHOLE
MOUNTING SLOT
5/16" DIA.
Back View