Herrtronic
®
Model 6000
I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
5
www.trioniaq.com
Key Features
Adjustable Setpoints (See Figure 7, Page 11)
Capacity
• Range = 50-100%
• Preset at 100% for 6000-1
• Preset at 50% for 6000-2
Low Drain Threshold
• Range = 50-100%
• Preset at 90%
Cycle Time
• Range = 30-180 seconds
• Preset at 60 seconds
Faults:
Overcurrent
• 138% of Rated Current
• System Shutdown
Fill System
• Fill valve open for 6 hours without achieving capacity
setpoint or cylinder full
• System Shutdown
End of Cylinder Life
• 6 hours of operation while on cylinder full without
achieving capacity setpoint.
• System Shutdown
•
Operation using water of less than 100 micromho is
not recommended.
•
Typically 500-2000 hours of cylinder operation can
be obtained. Your actual cylinder life may be higher
or lower depending on the exact composition of
your water supply.
HERRMIDIFIER
POWER, CYLINDER FULL,
AND SERVICE INDICATOR LIGHTS
INTERNAL CIRCUIT BREAKER
ON/OFF/DRAIN SWITCH
COVER INTERLOCK SWITCH
(PREVENTS UNIT OPERATION
WITH COVER OFF)
FILL SYSTEM
(INTEGRAL 1" AIR GAP PREVENTS
REVERSE SIPHONING TO POTABLE
WATER SUPPLY; "ADJUSTABLE
METERING VALVE ACCOMODATES
WATER PRESSURES UP TO 100 PSI."
ISOLATED CONTROL COMPARTMENT
WITH SOLID STATE CONTROLS
DRAIN SYSTEM
(SEALED DRAIN VALVE, ADJUSTABLE
DRAIN THRESHOLD AND CYCLE
TIME PROVIDE EXTENDED LIFE.)
CYLINDER - REPLACEABLE
GLASS FILLED POLYPROPYLENE
"CYLINDER FULL" ELECTRODE
(RED WIRE)
ADJUSTABLE LOUVER
INTEGRAL, QUIET
OPERATING FAN
CONCEALED FILL AND
DRAIN CONNECTIONS
INTEGRAL HUMIDISTAT