“LIVELINK INSTALL” APP / ROOM ADMINISTRATION / SETTINGS: ADVANCED SENSOR SETTINGS
Page 63 / 77
Parameter
Default
setting
Variables
Explanation
Pr
esenc
e det
ection
SwitchMode
SwitchBoth
Fully automatic operation
Semi-automatic operation
Fully/semi-automatic operation
Fully automatic: Switching on and off automatically
Semi-automatic: Switching off automatically,
switching on manually via push-button
shutOffDelay
5 minutes
0-60 minutes
Shut-off delay in minutes
switchOffTimeOut
0-3600
seconds
is set in the Use Case
Inverse time of presence detection. Time that must pass with-
out movement after a manual intervention in order to return to
automatic operation.
TurnOnValue
100 %
is set in the Use Case
Is part of the control. If the control is switched on again via a
presence sensor in “light mode”, this start value is used. In
case of a configuration that loads the default scene upon being
switched on, this value is pointless and is not being utilised
Cons
tant light c
ontr
ol
SwitchMode
SwitchBoth
SwitchBoth
OnlySwitchON
OnlySwitchOFF
Switching behaviour in case of sufficient daylight
SwitchBoth:
Switching on and off automatically in case
of a sufficient share of daylight
OnlySwitchOn:
No daylight-depending switching off,
the illumination remains at
a minimum level
OnlySwitchOFF: Automatic daylight-dependent switching
off, but not switching back on upon drop-
ping below the target value
ShutOFFDelay
300
0-3600 seconds
Shut-off delay at the control after exceeding the turn-off
threshold
TurnOffThreshold
25 %
0-100 %
Turn-off threshold, at which the system turns the illumination off
NominalValue
500 lx
0-1024 lx
Target value to which the system adjusts
(measured at the sensor)
Dogleg
235
0-254
Breakpoint at which the set offset is regulated to 0
SlowWindow
5
0-20
Range around the nominal value in which no control is exercised
SlowWindowStep
1
0-20
Step width around the nominal value
FastWindow
10
0-40
Other ranges in which control is exercised at reduced speed
FastWindowStep
3
0-20
Step width in other ranges
SpeedDown
2
0-20
Speed of adjusting down
SpeedUp
0
0-20
Speed of adjusting up
Summary of Contents for LiveLink
Page 1: ...LIVELINK SYSTEM MANUAL ...
Page 76: ...FAQ Page 76 77 ...