background image

Programming the daylight linked function

The dimming curve for daylight management is set via the modular

DIM DM

 

module or via the light sensor itself. Two values are stored, appropriate to  
the external lighting conditions, Twilight and Daylight set points. 
Two switches on the modular

DIM DM

 module represent these positions.  

Light levels for the programming of the daylight set points are set via the 
modular

DIM BASIC

 module.

Interior 
lighting

Control characteristics

Row I

Row II

Row III

Day

available
daylight

Night

100 %

0 %

Twilight system points

(System points A)

Daytime system points

(System points B)

Programming of day time system set point

The settings should be programmed under sufficient daylight conditions,  
preferably, when the row of luminaires nearest the window, are dimmed 
to their lowest possible setting to achieve the designed light level.

1.  Set desired light level for each row of luminaires I – III via  
 modular

DIM BASIC

.

2.  Select respective channels via selector switch on  
 modular

DIM DM

 module.

3.  Save the daytime system point by pressing (> 5 s) the Sun key (Sys B)  
  by means of e.g. a ball-point.
4.  Storage of the system point is acknowledged by the flashing of the  
  lighting source.
5.  For programming further channels, repeat steps 1–4.
6.  Select the channel you wish to control via daylight management by  
  selecting the appropriate channel or combinations of channels using 
  the selector switch on the modular

DIM DM

 module.

0 %

25 %

50 %

500 LUX
Artificial light
Daylight

Day

I

II

III

Programming of twilight set points

The settings should be programmed under twilight conditions, preferably, 
when hardly any daylight is present. Alternatively, the settings may be 
programmed during the day, with the daylight-sensor covered.

1.  Set desired light level for each row of luminaires I – II via 
 modular

DIM BASIC

.

2.  Select respective channels via selector switch on  
 modular

DIM DM

 module.

3.  Save the twilight system point by pressing (> 5 s) the Moon key (Sys A)  
  by means of e.g. a ball-point. 
4.  Storage of the system point is acknowledged by the flashing of the  
  lighting source.
5.  For programming further channels, repeat steps 1–4.
6.  Select the channel you wish to control via daylight management  
  by selecting the appropriate channel or combinations of channels  
  using the selector switch on the modular

DIM DM

 module.

I

II

III

80 %

90 %

100 %

500 LUX

Artificial light

Daylight

Twilight

6

Data sheet 08/14-CO061-3  We reserve the right to make technical changes without prior notice.

Summary of Contents for modularDIM SC

Page 1: ...t extension 1 temperature permitted ambient temperature C 0 50 The modularDIM BASIC control module is the basis of the modularDIM product range The three output channels can be controlled individually or together Simple installation since no programming is required Parallel connection of several switches enables user friendly dimming and ON OFF switching from several points The modularDIM BASIC co...

Page 2: ...ambient temperature C 0 50 Expansion module for modularDIM systems to control scenes Enables the recall and program ming of four light scenes via the modularDIM BASIC The switch inputs are SELV and any push to make switches can be used 5 year guarantee luxCONTROL modularDIM Switch inputs are safety low voltage SELV Any standard push to make switch may be used Packaging carton 1 pc s 2 Data sheet 0...

Page 3: ...odularDIM DM to the basic module to control up to three application specific luminaire groups Simple programming of each independent luminaire group 5 year guarantee accessories sensor DAYLIGHT article number 86454586 The modularDIM system includes an attractive and solid ceiling mounted sensor for the detection of sky brightness Its sensing aperture is aligned in the direction of the daylight 5 y...

Page 4: ...ls based on the galvanic isolation The modularDIM LC is designed as to build in unit for the integration into a switch cabinet This unit is easy to install Packaging carton 30 pc s type modularDIM LC article number 86457888 voltage V 220 240 frequency Hz 50 60 galvanic isolation spec 4000 V 2 min 6 mm SELV max output voltage V 30 permitted ambient temperature C 0 50 and to com mission because ther...

Page 5: ...ffort Therefore this important feature of the modularDIM LC gives now the opportunity to combine the modularDIM system with the common commercial of the shelf main rated presence detection PD units sensors PD 1 PD 3 potential free in order to the com contact because of the galvanic isolation modularDIM DM The modularDIM DM is an extension module powered directly by the modu larDIM BASIC module It ...

Page 6: ...m point is acknowledged by the flashing of the lighting source 5 For programming further channels repeat steps 1 4 6 Select the channel you wish to control via daylight management by selecting the appropriate channel or combinations of channels using the selector switch on the modularDIM DM module 0 25 50 500 LUX Artificial light Daylight Day I II III Programming of twilight set points The setting...

Page 7: ...D2 DA L N PCD 2 PCA 6 D1 DA D2 DA 3 4 7 D1 DA D2 DA L N TE one4all D1 DA D2 DA L N PCD modularDIM DM channel selector iX X2 AUTO S1 S2 S1 S2 X1 MAN Installation instructions To enable several operating points to be used several keys or switches are connected in parallel The maximum operating length of all keys as well as the light sensor may not be more than a max length of 100 m The DSI signal is...