www.tridonic.com
9
Subject to change without notice. Information provided without guarantee.
Data sheet 04/22-EM115-12
Emergency lighting units
EM LED Light Engines
8. Miscellaneous
8.1 Black Box data recording
Recording of several parameters only accessable for Tridonic.
8.2 Additional information
Additional technical information at www.tridonic.com
→
Technical Data
The light source of this luminaire is not replaceable; when the light source
reaches its end of life replace the whole luminaire. Lifetime declarations
are informative and represent no warranty claim. No warranty if device was
opened.
7. Optical properties
7.1 Anti panic
7.2 Escape route
Light distribution
Light distribution
Max. spacing for >0.5 lux
1
Height
Centre to end
2
Centre to centre
3
Trans
Axial
Trans
Axial
2.5 m
3.85 m
3.80 m
10.90 m
10.85 m
3.0 m
3.80 m
3.75 m
11.90 m
11.90 m
3.5 m
3.80 m
3.80 m
12.90 m
12.90 m
4.0 m
3.70 m
3.70 m
13.90 m
13.85 m
5.0 m
3.55 m
3.50 m
14.90 m
14.90 m
6.0 m
3.10 m
3.05 m
15.10 m
15.05 m
All values for ta = 30 °C
Luminous flux: 200 lm
1
Maintainance factor = 0.8, photometric data available on request
2
Distance between module and wall
3
Distance between two modules
-60°
-50°
-40°
-30°
-20°
-10°
10°
20°
30°
40°
50°
60°
70°
80°
90°
0
10
20
30
40
50
60
70
80
90
100
110
0°
20
-20
40
60
80 100
-40
-60
-80
-100
0
-60°
-50°
-40°
-30°
-20°
-10°
10°
20°
30°
40°
50°
60°
70°
80°
90°
0
10
20
30
40
50
60
70
80
90
100
110
0°
20
-20
40
60
80 100
-40
-60
-80
-100
0
rela
tiv
e int
ensity Iv
/Iv
,max
rela
tiv
e int
ensity Iv
/Iv
,max
Max. spacing for >1.0 lux
1
Height
Centre to end
2
Centre to centre
3
Trans
Axial
Trans
Axial
2.5 m
4.75 m
2.75 m
11.65 m
6.55 m
3.0 m
4.80 m
2.95 m
12.75 m
7.20 m
3.5 m
5.05 m
1.50 m
13.45 m
6.85 m
4.0 m
5.20 m
1.65 m
13.60 m
6.50 m
5.0 m
5.50 m
1.80 m
14.30 m
4.35 m
6.0 m
5.70 m
1.90 m
15.05 m
4.85 m
7.0 m
5.75 m
1.90 m
15.60 m
5.15 m
8.0 m
5.65 m
1.85 m
16.05 m
5.35 m
All values for ta = 30 °C
Luminous flux: 200 lm
1
Maintainance factor = 0.8, photometric data available on request
2
Distance between module and wall
3
Distance between two modules
C0 / C90 / C180 / 270
C0 / C180
C90 / C 270
7.3 Spot
Light distribution
-60°
-50°
-40°
-30°
-20°
-10°
10°
20°
30°
40°
50°
60°
70°
80°
90°
0
10
20
30
40
50
60
70
80
90
100
110
0°
20
-20
40
60
80 100
-40
-60
-80
-100
0
rela
tiv
e int
ensity Iv
/Iv
,max
Max. spacing for >0.5 lux / > 5 lux
1
Minimum
illuminance
Height
Centre to end
2
Centre to centre
3
Trans
Axial
Trans
Axial
0.5
2.5 m
1.05 m
1.90 m
8.40 m
4.30 m
3.0 m
2.35 m
1.25 m
5.35 m
5.20 m
3.5 m
2.80 m
1.45 m
6.25 m
6.05 m
4.0 m
1.70 m
1.70 m
7.90 m
5.85 m
5.0 m
2.10 m
2.05 m
8.90 m
8.40 m
6.0 m
2.30 m
2.30 m
8.15 m
8.10 m
7.0 m
2.50 m
2.45 m
8.00 m
8.00 m
8.0 m
2.65 m
2.60 m
7.80 m
7.85 m
5.0
2.5 m
0.85 m
0.80 m
2.50 m
2.45 m
3.0 m
0.90 m
0.85 m
2.55 m
2.55 m
3.5 m
0.90 m
0.90 m
2.75 m
2.75 m
4.0 m
0.90 m
0.95 m
2.95 m
2.95 m
5.0 m
0.95 m
0.90 m
3.30 m
3.25 m
6.0 m
0.95 m
0.90 m
3.50 m
3.45 m
7.0 m
0.85 m
0.85 m
3.60 m
3.55 m
8.0 m
0.75 m
0.75 m
3.60 m
3.60 m
All values for ta = 30 °C
Luminous flux: 200 lm
1
Maintainance factor = 0.8, photometric data available on request
2
Distance between module and wall
3
Distance between two modules
C0 / C90 / C180 / 270