Data sheet 07/20-EM071-10
Emergency lighting units
EM converterLED
3.5 Maximum lead length
LED
3 m (6 m loop)
Status indication LED 1 m
Batteries
1.3 m
4. Mechanical values
4.1 Housing properties
• Casing manufactured from polycarbonate.
• Type of protection: IP20
• Max. torque at the mounting screws: 0.8 Nm
4.2 Mechanical data accessories
LED status indicator
• Green
• Mounting hole 6.5 mm diameter, 1 – 1.6 thickness
• Lead length 0.3 m / 0.6 m / 1.0 m
• Insulation rating: 90 °C
• Plug connection
Test switch
• Mounting hole 7.0 mm diameter
• Lead length 0.55 m
• Plug connection
Battery leads
• Quantity: 1 red and 1 black
• Length: 1.3 m
• Wire type: 0.5 mm
2
solid conductor
• Insulation rating: 90 °C
Battery end termination
Push on 4.8 mm receptacle to suit battery
spade fitted with insulating cover
Module end termination
8.0 mm stripped insulation
Two-piece batteries are supplied with a 200 mm lead with 4.8 mm receptacle
at each end and insulting covers to connect the separate sticks together.
3.6 Use of different phases
The use of different phases for switched line and unswitched line is allowed.
When using different phases, the unswitched line must fail if the switched
line fails. This is required to assure correct switching into emergency mode. It
can be realised with a relay.