Data sheet 07/20-EM071-10
Emergency lighting units
EM converterLED
EM converterLED BASIC, 1 / 3 h
Type
EM converterLED BASIC
203 NiCd/NiMH 90V
EM converterLED BASIC
204 NiCd/NiMH 90V
Article no.
89800561
89800562
Cells
3 cells
4 cells
Duration
1 h
3 h
1 h
3 h
Technology
and capacity
Design
Number
of cells
Type
Article no.
Assignable batteries
NiCd 4 Ah
D cells
stick
1 x 3
Accu-NiCd 3A 55
28002773
•
side by side
3 x 1
Accu-NiCd 3B 55
89800384
•
stick
1 x 4
Accu-NiCd 4A 55
89800089
•
stick + stick
2 + 2
Accu-NiCd 4C 55
28002775
•
side by side
4 x 1
Accu-NiCd 4B 55
89800385
•
NiMH 2.2 Ah
Cs cells
stick
1 x 3
Accu-NiMH 3A
28002088
•
stick
1 x 4
Accu-NiMH 4A
28002089
•
NiMH 4 Ah
LA cells
stick
1 x 3
Accu-NiMH 4Ah 3A CON 89800441
•
stick
1 x 4
Accu-NiMH 4Ah 4A CON
89800442
•
EM converterLED BASIC, 1 / 3 h
Type
EM converterLED BASIC
203 NiCd/NiMH 90V
EM converterLED BASIC
204 NiCd/NiMH 90V
Article no.
89800561
89800562
Cells
3 cells
4 cells
Duration
1 h
3 h
1 h
3 h
Battery charge
time
Initial charge
24 h
Fast recharge
24 h
Trickle charge
continuously
Charging current
Initial charge
80 – 130 mA
170 – 220 mA
80 – 130 mA
170 – 220 mA
Fast recharge
80 – 130 mA
170 – 220 mA
80 – 130 mA
170 – 220 mA
Trickle charge
45 – 95 mA
80 – 130 mA
45 – 95 mA
80 – 130 mA
Discharge current
850 – 960 mA
850 – 960 mA
850 – 960 mA
850 – 960 mA
Charge voltage range
1
0.9 – 1.65 V per cell
Discharge voltage range
1.65 – 0.90 V per cell
1
The battery will be charged below 0.9 V. The EM converterLED will indicate a battery fault.
The emergency lighting LED Driver will recharge the battery normally after running the test of 61347-2-7 CL 22.3
(abnormal operating conditions).