Data sheet 09/22-EM122-3

Emergency lighting units

EM converterLED

Commissioning

After installation of the luminaire and initial connection of the mains supply 
and battery supply to the EM converterLED PRO the unit will commence 
charging the batteries for 24 hours (initial charge). Afterwards the module 
will conduct a commissioning test for the full duration. The 20 hours rechar-
ge occurs also if a new battery is connected or the module exits the rest 
mode condition. The following automatic commissioning duration test is only 
performed when a battery is replaced and fully charged (after 20 hrs) and 
the interval time is not set to zero, otherwise the system is expected to per-
form the testing.

Functional test

The time of day and frequency of the 5 seconds function test can be set by 
the DALI controller. The default setting is a 5 seconds test on a weekly basis.

Duration test

The time of day and frequency of the duration test can be set by the DALI 
controller. The default setting is a duration test conducted every 52 weeks.

For 2 h operation:
The first commissioning duration test has a time of 120 minutes, subse-
quent through life tests are conducted for 90 minutes. When the battery is 
changed or disconnected and re-connected the unit will next conduct a 120 
minute test.

Prolong time

Prolong time can be set by the DALI controller.  This is the delay time bet-
ween return of the mains supply and the end of the emergency operation. 
The default prolong time is set as 0 minutes as specified within the DALI 
standard.
Indicator LED will stay off for the duration of the prolong time.

Test switch

An optional test switch can be wired to each EM converterLED.  
This can be used to to:
•  Initiate a 5 seconds function test: 

press 200 ms < T < 1 s

•  Execute function test as long as switch pressed:  press > 1 s
•  Reset selftest timer (adjust local timing): 

press > 10 s

Rest Mode / Inhibit Mode

Emergency operation is automatically started when the mains supply is 
switched off. If the Rest Mode is activated, the discharging of the battery will 
be minimized by switching off the LED output. If the Inhibit Mode has been 
activated before the mains supply is switched off, Rest Mode will be automa-
tically switched on if the mains supply is switched off within 15 minutes.
Rest Mode and Inhibit Mode can be initiated by the DALI controller. The 
REST command has to be sent after the mains supply has been discon-
nected and whilst the EM converterLED PRO is in emergency operation. 
The INHIBIT command has to be sent while the EM converterLED PRO is 
supplied by mains.
After a mains reset the EM converterLED PRO exits the Rest Mode. Rest 
Mode and Inhibit Mode can both be disabled by sending the RE-LIGHT/
RESET INHIBIT command.

Timer reset functionality

The timer for function and duration test can be set to a particular time of the 
day by either pressing the test switch for longer than 10 seconds or cycling 
the unswitched line supply 5 times within 1 minute. The timer adjustment 
will enable the test start time to be defined manually at time in day when 
the timer was reset. It will also disable the adaptive test algorithm thereby 
forcing the unit to perform the test at the same time rather than it being 
defined by the adaptive algorithm. This function will only work provided the 
interval time is greater than zero (automatic test mode enabled). The delay 
timer value set when the unit was commissioned will be reloaded in order to 
randomise the tests between adjacent units.

 

DALI Controller

DALI controllers and hardware/software solutions are available from  
Tridonic. Please refer to the Lighting controls section.

Summary of Contents for 89800832

Page 1: ...le with plug duration link Compatible with most constant current LED drivers see 5 4 3 pole technology 2 pole LED module changeover and delayed power switching for the LED driver Automatic shutdown of output if LED load is out of range Constant power output Addressing function patented EZ easy addressing Two colour status display LED Electronic charge system Deep discharge protection Short circuit...

Page 2: ...198 264 V Mains frequency 50 60 Hz LED module forward voltage range 15 54 V Output current see chapter 5 3 Starting time 0 5 s from detection of emergency event Overvoltage protection 320 V for 48 h U OUT including open short circuit and double load 60 V Max open circuit voltage 60 V Ambient temperature range ta 25 55 C Max casing temperature tc 80 C Mains voltage changeover threshold according to...

Page 3: ...le jacket diameter 2 2 9 mm Ordering data Type Article number Packaging carton Packaging pallet Weight per pc EMcLED SR 28003813 10 pc s 1 260 pc s 0 08 kg Product description Optional strain relief set for independent applications Transforms the LED driver into a fully class II compatible LED driver e g ceiling installation Easy and tool free mounting to the LED driver screwless cable clamp chann...

Page 4: ...ng data Type Article number Packaging bag Packaging carton Weight per pc LED EM bi colour 1 0 m CON 89800273 25 pc s 200 pc s 0 015 kg LED EM bi colour high brightness HO 1 0 m CON 89800275 25 pc s 200 pc s 0 015 kg LED EM bi colour 0 6 m CON 89800474 25 pc s 200 pc s 0 005 kg LED EM bi colour high brightness HO 0 6 m CON 89800475 25 pc s 200 pc s 0 005 kg LED EM bi colour 0 3 m CON 89800274 25 pc...

Page 5: ...ergency lighting units EM converterLED Product description Extension cable for LiFePO4 batteries Cable length 500 mm 3 pole plug connection Extension Cable LiFePO4 ACCES SORIES Ordering data Type Article number Packaging bag Packaging carton Weight per pc EXTENSION CABLE LiFePO4 500mm 28002461 10 pc s 200 pc s 0 01 kg ...

Page 6: ...age to the electronic devices this test must not be conducted 2 Thermal details and lifetime 2 1 Lifetime Average lifetime 50 000 hours under rated conditions with a failure rate of less than 10 Average failure rate of 0 2 per 1000 operating hours Expected lifetime EMcLED PRO HP 6W 50V tc 70 C 75 C 80 C lifetime 100 000 h 100 000 h 100 000 h EMcLED PRO HP 9W 50V tc 70 C 75 C 80 C lifetime 100 000 ...

Page 7: ...r LED Not connected Not connected LED driver LED LED LED driver Battery Battery LED Module Emergency One LED module is operated in emergency mode All LED modules are operated in mains mode Neutral P O Lout Lin N Dali Dali L L N EM converterLED PRO Neutral Dali Dali Un Switched Line Test switch Indicator LED Switched Line out Switched Line in LED driver LED LED LED driver Battery Battery LED Module...

Page 8: ...ch Indicator LED LED driver LED LED LED driver Battery Battery LED Module Emergency LED Module LED Module LED driver max 300 W in operation Lout Lin N Dali Dali L Neutral Dali Dali Un Switched Line Switched Line out Switched Line in EM converterLED PRO with a DALI LED driver and one LED module for mains and emergency operation Neutral P O Lout Lin N Dali Dali L L N Dali Dali EM converterLED PRO Ne...

Page 9: ...insulation 6 mm creepage and clearance when these connections should be kept SELV The output to the LED is DC but has high frequency content which should be considered for good EMC compliance Separate LED leads from the mains and DALI connections and wiring for good EMC performance Maximum lead length on the LED terminals is 3 m For a good EMC performance keep the LED wiring as short as possible R...

Page 10: ...FePO4 battery 2S1P 6 4 V battery voltage 3 h application LiFePO4 battery 3S2P 9 6 V battery voltage EMcLED PRO HP 6W 50V Article number 89800832 1 h application LiFePO4 battery 2S1P 6 4 V battery voltage 3 h application LiFePO4 battery 2S2P 6 4 V battery voltage VLED V VLED V LED current mA LED current mA 0 20 40 10 30 50 60 100 200 300 400 500 0 600 700 0 20 40 10 30 50 60 50 100 150 200 250 300 ...

Page 11: ...tests at individually selected times Status flags are set for report back and data logging of results When a DALI bus has not been connected or when a DALI bus is connected but the DALI default DELAY and INTERVAL times have not been re set by sending appropriate DALI commands then the EM converterLED PRO will conduct self tests in accordance with the default times set within the EEPROM These defau...

Page 12: ...onverterLED This can be used to to Initiate a 5 seconds function test press 200 ms T 1 s Execute function test as long as switch pressed press 1 s Reset selftest timer adjust local timing press 10 s Rest Mode Inhibit Mode Emergency operation is automatically started when the mains supply is switched off If the Rest Mode is activated the discharging of the battery will be minimized by switching off...

Page 13: ...ger off 0 mA when battery voltage exceeds 3 6 V Note Battery protected against operation at excessive temperatures charging stopped when battery cell temperature 5 C or 60 C The emergency lighting LED driver will recharge the battery normally after running the test of 61347 2 7 CL 22 3 abnormal operating conditions 2 The battery will not be charged below 2 0 V 3 The discharge current varies depend...

Page 14: ...rminals FELV control terminals marked Risk of electric shock are not safe to touch Insulate circuits connected to any FELV control terminal for the Low Voltage supply voltage of the control gear Protect terminals connected to the FELV circuit against accidental contact 8 5 BlackBox data recording Several parameters in respect to the application and use of the product are stored in the EM converter...

Reviews: