www.tridonic.com
10
Subject to change without notice. Information provided without guarantee.
Data sheet 09/22-EM122-3
Emergency lighting units
EM converterLED
5. Electrical values
5.1 Maximum loading of automatic circuit breakers
Automatic circuit breaker type
B10
B13
B16
B20
C10
C13
C16
C20
Inrush current
Installation Ø
1.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
I
max
time
EMcLED PRO
90
130
130
130
180
260
260
260
10 A
120 μs
5.3 Typ. LED current/voltage characteristics
The LED current in emergency mode is automatically adjusted by the EM converterLED module based on the total forward voltage of the LED modules con-
nected and the associated battery. The start of the LED in emergency mode does not result in a current peak.
EMcLED PRO HP 9W 50V
Article number: 89800834
1 h application
LiFePO4 battery 2S1P, 6.4 V battery voltage
3 h application
LiFePO4 battery 3S2P, 9.6 V battery voltage
EMcLED PRO HP 6W 50V
Article number: 89800832
1 h application
LiFePO4 battery 2S1P, 6.4 V battery voltage
3 h application
LiFePO4 battery 2S2P, 6.4 V battery voltage
V
LED
[V]
V
LED
[V]
LED curr
ent [mA]
LED curr
ent [mA]
0
20
40
10
30
50
60
100
200
300
400
500
0
600
700
0
20
40
10
30
50
60
50
100
150
200
250
300
350
0
400
450
5.2 Insulation matrix
When using a non-SELV LED driver insulate the battery, LED, test switch and indicator LED in the luminaire according to the
U-OUT rating of the LED driver.
DALI terminals are not SELV. Wire the terminals in accordance with the requirements of low voltage installations.
Max. LED current at nominal battery voltage
Min. LED current at nominal battery voltage
Mains
Switched Live
Battery, LED, Test
switch, Indicator LED
DALI
LED driver
Mains
–
•
• •
•
• •
Switched Live
•
–
• •
•
• •
Battery, LED, Test
switch, Indicator LED
• •
• •
–
•
•
DALI
•
•
•
–
• •
LED driver
• •
• •
–
• •
–
• Represents basic insulation
• • Represents double or reinforced insulation