![Tridonic 89800598 Manual Download Page 8](http://html.mh-extra.com/html/tridonic/89800598/89800598_manual_1162246008.webp)
www.tridonic.com
8
Subject to change without notice. Information provided without guarantee.
Data sheet 12/20-EM083-11
Emergency lighting units
EM powerLED
5. Electrical values
Automatic circuit breaker type
C10
C13
C16
C20
B10
B13
B16
B20
Inrush current
Installation Ø
1.5 mm
2
1.5 mm
2
2.5 mm
2
2.5 mm
2
1.5 mm
2
1.5 mm
2
2.5 mm
2
2.5 mm
2
I
max
time
EM powerLED BASIC FX 2xx lp 75W 220V
12
18
24
28
6
9
12
14
25.8 A
280 µs
5.1 Maximum loading of automatic circuit breakers
Calculation uses typical values from ABB series S200 as a reference.
Actual values may differ due to used circuit breaker types and installation environment.
Insulate the battery, LED, test switch and indicator LED in the luminaire according to the U-OUT rating of the LED Driver.
5.2 Insulation matrix
Mains
Switched Live
Battery, LED, Test
switch, Indicator LED
I-SELECT 2
Mains
–
•
• •
•
Switched Live
•
–
• •
•
Battery, LED, Test
switch, Indicator LED
• •
• •
–
• •
I-SELECT 2
•
•
• •
–
• Represents basic insulation
• • Represents double or reinforced insulation