Data sheet 12/20-EM083-11
Emergency lighting units
EM powerLED
Specific technical data
Type
2
Number
of battery
cells
Output
current
3 4
Min. forward
voltage
5
Max. forward
voltage
5
Output
power
Typ. power consumption
(at 230 V, 50 Hz, full load)
Typ. current consumption
(at 230 V, 50 Hz, full load)
λ (at 230 V, 50 Hz,
full load)
I-select 2
resistor value
7
Normal operation
EM powerLED BASIC FX 213 / 214 / 215 /
233 / 234 / 235 lp 75W 220V
–
80 mA
75 V
220 V
20 W
20 W
100 mA
0.85C
open
–
100 mA
50 V
220 V
33 W
27 W
135 mA
0.90C
33.33 kΩ
–
150 mA
50 V
220 V
33 W
37 W
170 mA
0.95
33.33 kΩ
–
200 mA
50 V
220 V
44 W
49 W
220 mA
0.95
25.00 kΩ
–
250 mA
50 V
220 V
55 W
60 W
270 mA
0.97
20.00 kΩ
–
300 mA
50 V
220 V
66 W
71 W
320 mA
0.97
16.67 kΩ
–
350 mA
50 V
214 V
75 W
82 W
360 mA
0.98
14.29 kΩ
–
400 mA
50 V
188 V
75 W
82 W
370 mA
0.98
short circuit
(0 Ω)
Emergency operation
EM powerLED BASIC FX
213 / 233 lp 75W 220V
3
see page 8
50 V
220 V
2.5 W
–
–
all
EM powerLED BASIC FX
214 / 234 lp 75W 220V
4
see page 8
50 V
220 V
3.5 W
–
–
all
EM powerLED BASIC FX
215 / 235 lp 75W 220V
5
see page 8
50 V
220 V
4.5 W
–
–
all
1
Depending on the selected output current.
2
EM = Emergency
3
The table only lists a number of possible operating points but does not cover each single point. The output current can be set within the total value range in 1-mA-steps.
4
Output current is mean value.
5
Output voltage range defined in normal operation.
6
Ambient temperature range ta defined in normal operation
7
Not compatible with I-select (generation 1).