TriangleTube Prestige Trimax 175 Installation Instructions Manual Download Page 6

6

PRESTIGE IGNITION KIT - INSTALLATION INSTRUCTIONS

Fig. 9 - Spark Generator and Bracket (PT 175)

Fig. 10 - Throttle and Offset Locations

NG

LP

H

igh F

ire

CO2

9.5%

11.2%

O2

4.0%

4.0%

CO

< 100 ppm

<100 ppm

Lo

w F

ire

CO2

9.5%

11.2%

O2

4.0%

4.0%

Table 3 - Recommended Combustion Levels

•  If the CO2 combustion level during low fire 

(1%) differs by more than 0.4% from the 
recommended combustion setting  (See 

Table 

3

), remove plastic cover from Offset screw (See 

Fig. 10

) and adjust as follows: 

•  Counter-clockwise adjustment of the offset 

screw at Low Fire : O2 increases, CO2 decreases

•  Clockwise adjustment of the offset screw at 

Low Fire : O2 decreases, CO2 increases.

1.5.10  Return to Service

1.  Reinstall the air intake on the venturi.
2.  Close top access panel, as required.
3.  Check that all wiring connections are secure.
4.  Check that the gas connection is tight.
5.  Supply power to the boiler through the external elec-

tric box.

6.  Open gas supply.
7.  Turn boiler on using the boiler On/Off switch.
8.  Perform any required configuration change in the Tri-

Max setup  according to the initial settings indicated 
in 

“Default Values and Adjustments” on page 8

.

9.  Reinstall the boiler front panel. 
10.  On the rating plate of the appliance, install the 

sticker provided with the kit. This will indicate that 

the boiler has been upgraded with the ignition kit, 

for future reference.

Fig. 11 - Prestige Solo & Excellence - Rating Plate Correction

PU

Stick here

B

C

A

Offset

Throttle

(Remove 

plastic cover 

to access 

screw)

Summary of Contents for Prestige Trimax 175

Page 1: ...x 20 Flue gas analyzer 1 4 2 Preparation Procedure 1 Turn the boiler off by pressing the on off power switch 2 Allow boiler to cool down 3 Disconnect electrical power at the external electric box Avoi...

Page 2: ...W Bk V Fig 3 Prestige Solo Excellence Ignition Kit Item Description Qty 1 Igniter 1 Screws igniter 2 Gasket igniter 1 Bracket spark generator not illustrated 1 2 Spark generator 1 3 Wiring spark gene...

Page 3: ...r intake 3 from venturi Retain for reinstallation Before disconnecting any wire connections mark and label all connections and location of the connections 2 Open top access panels by removing top acce...

Page 4: ...Required 0 221 5 6mm Table 2 Orifice Sizes 1 5 4 Removing the Burner and Insulation 1 Remove heat exchanger bracket located at the back of the heat exchanger Discard bracket 2 Remove burner plate nut...

Page 5: ...nnection 1 5 9 Checking the Combustion Settings 1 Turn boiler on 2 Allow the appliance to stabilize and insert the gas an alyzer probe in the top vent adapter measuring port 3 Check combustion values...

Page 6: ...s 1 5 10 Return to Service 1 Reinstall the air intake on the venturi 2 Close top access panel as required 3 Check that all wiring connections are secure 4 Check that the gas connection is tight 5 Supp...

Page 7: ...llence PCB Wiring POSTMOD Gr Br W Bk V F00 F01 V To left side casing grounding tabs Connect to uncon nected Molex connector in exist ing boiler wiring DO NOT reconnect original boiler wiring Molex con...

Page 8: ...68 F 20 C 188 F 87 C CH1 Minimum Setpoint 120 F 49 C 60 F 15 C 188 F 87 C Reset Curve Coldest Day 0 F 18 C 30 F 34 C 50 F 10 C Reset Curve Warmest Day 64 F 18 C 60 F 15 C 78 F 25 C CH2 Circuit Enable...

Reviews: