background image

4

PRESTIGE SOLO & EXCELLENCE IGNITION KIT - INSTALLATION INSTRUCTIONS

1.5.  Kit installation

1.5.1  Required tools and material

• 

Wrench, Torx, 25

• 

Wrench, 10 mm

1.5.2  Installation of Igniter and Spark Generator

1.  Install the new igniter, with its new gasket, on the 

burner mounting plate support (See 

Fig. 4)

.

2.  Tighten 2 igniter screws by hand, then torque 

screws between 13 and 18 lbf-in. 

Do not exceed the recommended max. torque 

value for the igniter attachment screws to pre-

vent the igniter stems from distorting.

3.  Connect the ignition wire to the spark generator (

1

). Slide 

the protection sleeve (

2

) over the connector (See 

Fig. 5)

.

Fig. 4 - Prestige Solo & Excellence - New igniter Installation

4.  Remove the blower clamp screw (

A

). Retain for rein-

stallation. (See 

Fig. 6)

.

Fig. 5 - Prestige Solo & Excellence - Ignition Wire Connection

1

2

5.  Locate the spark generator with bracket (

B

) on the 

blower clamp (

A

), aligning bracket hole with blow-

er clamp hole. (See 

Fig. 6)

.

6.  Reinstall the blower clamp screw (

A

) to secure 

the spark generator bracket to the blower clamp. 

Torque screw between 62 and 71 lbf-in.

7.  Install the igniter cable boot so that the cable is 

smooth with no sharp bends and doesn’t curl on 
itself. See 

Fig. 7 &

 

Fig. 8. 

8.  Connect the spark generator connector (

C

) to the 

new igniter. 

A

B

C

Fig. 6 - Prestige Solo & Excellence - Spark Generator Installation

Fig. 7 - Prestige Solo  155 to 399 - Igniter Kit Installed

Fig. 8 - Prestige Solo &  Excellence - Igniter Cable Installation

OK

NO

1.5.3  Printed Circuit Board replacement

1.  Disconnect violet wire (ionization current return) 

(See 

Fig. 13

) from circuit board ground connection. 

Discard the wire.

2.  Disconnect all wire terminals from the board.

3.  Remove the circuit board and discard according to 

applicable local regulations (See 

Fig. 9

).

4.  Install new circuit board, making sure it is secured in 

the retaining clips (See 

Fig. 10

).

NOTICE

Summary of Contents for Prestige PA 299 V1

Page 1: ...ds 1 1 V1 and V2 PA299 and PA399 Boilers There are two different blower venturi arrangements that result in two different required ignition kits The separate blower and venturi V2 configuration ap pli...

Page 2: ...ed 2 6 PB Sticker S N adaptation not shown 1 7 Combustion Chamber Insulation gasket not shown 1 Fig 1 Prestige Solo Excellence Ignition Kit Gr Br W Bk V 4 5 6 1 2 3 X15 X11 6 7 8 9 10 1 2 3 4 5 3 4 1...

Page 3: ...ing the power switch 5 Disconnect electrical power at the external electric box Avoid electrical shock by disconnecting the electrical supply prior to performing any operation on the internal parts of...

Page 4: ...spark generator with bracket B on the blower clamp A aligning bracket hole with blow er clamp hole See Fig 6 6 Reinstall the blower clamp screw A to secure the spark generator bracket to the blower cl...

Page 5: ...x front cover See Fig 11 13 Connect the brown ionization cable at the front of the control box See Fig 11 14 Reuse the Control Board box to ship the old control board to Triangle Tube and using the pr...

Page 6: ...Excellence PCB Wiring Pre modification Protect bare pins with Fast on connectors then store connector and wiring at the rear of control box with retaining clips 4 5 6 1 2 3 X15 X11 6 7 8 9 10 1 2 3 4...

Page 7: ...7 PRESTIGE SOLO EXCELLENCE IGNITION KIT INSTALLATION INSTRUCTIONS A B Fig 15 Prestige Solo Excellence Combustion chamber 2 in 1 Insulation Damages...

Page 8: ...21 5 22 6 23 8 25 10 11 24 ALARM Pump 3 Flex Relay 3 to be set to MIX OPEN MIX OPEN ON ONLY if no additional pump is con nected to Flex Relay 3 P3 If a pump is connected please con tact your TTP assi...

Page 9: ...Off DHW ECS SWW Off MIX OPEN Off MIX CLOSE Off ERROR On FLAME Off Save Exit Boiler Settings Boiler Settings Prestige Model Solo Lockout Temp 105 C Modbus Address 1 Pump settings Pump Settings Current...