1

Prestige

Off Board Spark Ignition Kit

Installation Instructions

Kit Part Number

Kit numbers vary based on boiler size. Additional differ-
ences are needed at higher altitudes. Use the table be-
low to confirm the correct replacement kit is installed 
on the boiler. 

Low Altitude 

(0 - 5,000 ft)

Hi Altitude 

(5,000 + ft)

PA 80

PARKIT141

PARKIT151

PA 110

PARKIT142

PARKIT152

PA Excellence

PARKIT142

PARKIT152

PA 155

PARKIT143

PARKIT153

PA 175

PARKIT144

PARKIT154

PA 250

PARKIT145

PARKIT155

PA 299 V2*

PARKIT146

PARKIT156

PA 399 V2*

PARKIT147

PARKIT157

PA 299 V1*

PARKIT148

PARKIT158

PA 399 V1*

PARKIT149

PARKIT159

Table 1 - Kit Numbers

*See paragraph 1.1 for more details. 

DANGER

!

 

Indicates the presence of a hazardous situa-
tion which, if ignored, will result in substantial  
property damage, serious injury, or death.

WARNING

!

Indicates a potentially hazardous situation 
which, if ignored, can result in serious  injury or 
substantial property damage.

NOTICE

Indicates special instructions on installation, opera-

tion or maintenance, which are important to equip-

ment but not related to personal injury hazards.

1.1.  V1 and V2 PA299 and PA399 Boilers 

There are two different blower/venturi arrangements 

that result in two different required ignition  kits. The 

separate blower and venturi (V2) configuration ap-

plies to PA299s and PA399 with serial numbers after 

PA11700. Units with serial numbers below PA117000 

have a single piece blower venturi (V1). Some V1 

models may have been converted to the V2 config-

uration as well. 

Before installing the ignition kit, confirm your blow-

er/venturi configuration. See Engineering Bulletin 

dated Oct. 24, 2018 for more information.

WARNING

!

Installation of the wrong replacement kit will 

cause the improper operation of the boiler re-

sulting in substantial property damage, serious 

injury, or death.

1.2.  Purpose

This kit (see 

Fig. 1 

for details) replaces the existing ignit-

er and its wiring, as well as the printed circuit board and 
the front cover of the control box on all Prestige boilers .

NOTICE

This modification disables the Alarm Relay 

function which is used in several system con-

figurations. Therefore, to allow the heating sys-

tem configuration to be operational, some wire 

connections must be modified and some CTRL-

Max settings changed, as required. Please refer 

to paragraph 1.6 for more information.

Revision Date: 5/16/2019

2019-12 Prestige Igniter Replc.

Summary of Contents for Prestige PA 299 V1

Page 1: ...ds 1 1 V1 and V2 PA299 and PA399 Boilers There are two different blower venturi arrangements that result in two different required ignition kits The separate blower and venturi V2 configuration ap pli...

Page 2: ...ed 2 6 PB Sticker S N adaptation not shown 1 7 Combustion Chamber Insulation gasket not shown 1 Fig 1 Prestige Solo Excellence Ignition Kit Gr Br W Bk V 4 5 6 1 2 3 X15 X11 6 7 8 9 10 1 2 3 4 5 3 4 1...

Page 3: ...ing the power switch 5 Disconnect electrical power at the external electric box Avoid electrical shock by disconnecting the electrical supply prior to performing any operation on the internal parts of...

Page 4: ...spark generator with bracket B on the blower clamp A aligning bracket hole with blow er clamp hole See Fig 6 6 Reinstall the blower clamp screw A to secure the spark generator bracket to the blower cl...

Page 5: ...x front cover See Fig 11 13 Connect the brown ionization cable at the front of the control box See Fig 11 14 Reuse the Control Board box to ship the old control board to Triangle Tube and using the pr...

Page 6: ...Excellence PCB Wiring Pre modification Protect bare pins with Fast on connectors then store connector and wiring at the rear of control box with retaining clips 4 5 6 1 2 3 X15 X11 6 7 8 9 10 1 2 3 4...

Page 7: ...7 PRESTIGE SOLO EXCELLENCE IGNITION KIT INSTALLATION INSTRUCTIONS A B Fig 15 Prestige Solo Excellence Combustion chamber 2 in 1 Insulation Damages...

Page 8: ...21 5 22 6 23 8 25 10 11 24 ALARM Pump 3 Flex Relay 3 to be set to MIX OPEN MIX OPEN ON ONLY if no additional pump is con nected to Flex Relay 3 P3 If a pump is connected please con tact your TTP assi...

Page 9: ...Off DHW ECS SWW Off MIX OPEN Off MIX CLOSE Off ERROR On FLAME Off Save Exit Boiler Settings Boiler Settings Prestige Model Solo Lockout Temp 105 C Modbus Address 1 Pump settings Pump Settings Current...

Reviews: