INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS

5.  Combustion Test and Adjustments

NOTICE

The installer MUST perform a complete combustion check to 

ensure the following combustion levels are met at high and 

low input firing rates and the burner is operating at optimum 

conditions.

WARNING

!

The combustion testing and adjustments must be 

performed by a qualified installer, service agency or 

the gas supplier. All combustion measurements must 

be performed with calibrated equipment to ensure 

proper readings and accuracy.  Refer to Table 1 to 

check the combustion is within the acceptable range.

WARNING

!

Failure to perform a complete combustion test at both 

high and low input rates may result in incomplete 

combustion and the production of carbon monoxide, 

which can cause severe personal injury, death or 

substantial property damage.

1.  Touch simultaneously on the up and down soft 

keys for 3 seconds to access the functions for the 

installer. See Fig. 5.

2.  Enter the installer access code “054” by using the 

LEFT and RIGHT buttons to select a digit and the UP 

and DOWN buttons to change the digit.  Press the 

CENTER button to enter the access code.

3.  Press the RIGHT button to highlight the Manual 

Operation icon then press the CENTER button.

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

Manual Operation

Released

Off

Off

Off

CH1

FAN

DHW

CH2

Manual Operation

Released

Off

Off

Off

CH2

FAN

DHW

CH1

Manual Operation

Released

Off

Off

Off

DHW

FAN

CH1

CH2

Fig. 6:  CTRLMax Manual Operation

4.  Press the CENTER button while the FAN icon is 

highlighted to manually fire the burner and power 

the CH circulator. See Fig. 6.

NOTICE

An adequate CH load must be present to dissipate the heat 

generated during the combustion test. If an adequate CH 

load is not available, an indirect water heater can be used to 

dissipate the heat by creating a DHW call which will enable the 

DHW circulator.

5.  Press the RIGHT button to adjust the firing rate to 

100% (high fire).  Hold down the  RIGHT button to 

rapidly increase the firing rate.

6.  If the combustion levels during high fire are outside 

the recommended combustion settings (see Table 1), 

adjust the THROTTLE SCREW (see Fig. 7) using a flat-

blade screwdriver as follows:

Counter-clockwise adjustment of the THROTTLE 

SCREW at High Fire (100% firing rate):

 O

2

 decreases and CO

 increases

Clockwise adjustment of the THROTTLE SCREW at 

High Fire (100% firing rate):

 O

2

  increases and CO

2

 decreases

7.  Once the combustion level is set at high fire, manually 

place the boiler into low fire mode by pressing the 

LEFT button to adjust firing rate down to 1% (low 

fire).

8.  If the combustion level (O

2

 or CO

2

) during low fire is 

outside the recommended combustion settings in 

Table 1 contact Triangle Tube Technical Support.

9.  Press the CENTER button while the fan icon is 

highlighted to shutdown the burner. 

10. Press the LEFT or RIGHT button to highlight the home 

screen icon to exit the service mode. 

11. Replace the front panel and put the boiler back into 

operation.

Summary of Contents for INSRKIT08

Page 1: ...llow instructions below can result in severe personal injury or damage if ignored Instructions are for a qualified installer service technician only Read all instructions before proceeding Follow instructions in proper order NOTICE These instructions cover NG to LP conversion for Instinct boilersonly Eachkitissuppliedwithoneventurisuitable for use with that particular boiler model Kit Part Number ...

Page 2: ...e Acoustic Foam NOTICE The acoustic foam is only applicable to the 110 and 155 models The Instinct 199 models do NOT use the additional acoustic foam 1 Cut a 7 length of 3 diameter air inlet piping 2 Insert the 7 pipe into the air inlet adaptor Theacousticfoamshouldbeflushtotheinsideoftheairinlet adapter NOTICE The INSTINCT boiler has a length of acoustic foam already installed in the air inlet ad...

Page 3: ...askets must be reinstalled along with the pipe Use care not to damage the gaskets 4 Using a 10 mm socket and ratchet remove the three 3 bolts securing the venturi to the fan assembly and remove the natural gas venturi from the unit making sure not to damage the blower O ring gasket 4 Install the propane venturi 1 Verify the following when aligning the propane venturi 1 The UP arrow on the plastic ...

Page 4: ...boiler which can result in substantial property damage serious injury or death 6 Open the manual gas shut off valve to the unit Before placing the boiler back into operation test all gas connections for leaks and repair if leaks are found WARNING Do not check for gas leaks with an open flame Use a bubble test Failure to test for gas leaks can result in substantial property damage serious injury or...

Page 5: ...ff CH1 FAN Fig 6 CTRLMax Manual Operation 4 Press the CENTER button while the FAN icon is highlighted to manually fire the burner and power the CH circulator See Fig 6 NOTICE An adequate CH load must be present to dissipate the heat generated during the combustion test If an adequate CH load is not available an indirect water heater can be used to dissipate the heat by creating a DHW call which wi...

Page 6: ...Range 5 7 4 2 O2 Target 4 5 CO Max 200 ppm 10 8 CO2 Low Fire CO2 Range 10 0 11 0 CO2 Target 10 8 10 4 Target values are equivalent to High Fire values ensure CO values measured are less than or equal to High Fire CO measurements O2 Range 5 7 4 2 O2 Target 4 5 5 1 Target values are equivalent to High Fire values ensure O values measured are higher than or equal to High Fire O measurements CO Max 10...

Reviews: