19
INSTALLATION
Length of Pipe
Capacity of Pipe in Cubic Feet of Gas Per Hour
in Feet
(based on 0.60 specific. gravity, 0.30" w.c. pressure drop )
SCH 40
1/2"
3/4"
1"
1-1/4"
1-1/2"
10
132
278
520
1050
1600
20
92
190
350
730
1100
30
73
152
285
590
860
40
63
130
245
500
760
50
56
115
215
440
670
75
45
93
175
360
545
100
38
79
150
305
460
150
31
64
120
250
380
Table 2: Gas piping sizing - natural gas
•
For additional piping schedules, see
ANSI Z223.1
•
Canadian installations must comply
with CAN/CGA B149.1 or B149.2
Installation Code.