Trianco EuroStar Band A Operation Manual Download Page 27

COMMISSIONING

 

 
Although  all  burners  are  tested  before  despatch, 
individual site conditions

—such as oil supply pressures 

and  deviations  in  the  draught

—mean  that  the  burner 

will  require  adjustment  after  installation  to  achieve 
optimal  performance.  As  such,  the  boiler 

must

  be 

commissioned 

by 

qualified 

engineer, 

preferably 

OFTEC-trained  and  registered.  See  the  burner  setup 
leaflet for further information. 
 
It  is  the  responsibility  of  the  installation  engineer  to 
ensure the boiler is commissioned. Failure to do so will 
invalidate the guarantee and any extended warranty. 
 

Procedure 

 

 

Switch off the electrical supply to the boiler. 

 

 

Ensure  the  boiler  is  full  of  water  and  that  all 
isolation valves are open. 

 

 

Remove  the  combustion  chamber  access  cover 
and check the baffle positions (

figs 29 

&

 30

). 

 

 

For  single-pipe  oil  supplies,  disconnect  the  supply 
line  from  the  burner.  Open  the  shut-off  valve  and 
run a small quantity of oil into a container to ensure 
it is clean and free of air. Reconnect the oil supply. 

 

 

Check  that  the  programmer  is  in  the 

ON

  position 

and that any thermostats are calling for heat. 

 

 

Switch  on  the  electrical supply  to  the boiler,  which 
should now fire. 

 

Note:

 upon first firing, the burner may lockout due 

to  the  retention  of  air  in  the  oil  pump.  Should  this 
occur,  wait  for  one  minute  before  pressing  the 
reset  button.  Should  the  burner  lockout  again,  the 
air can be bled from the oil pump via the pressure 
gauge connection. 

 

 

Start and stop the burner several times. When the 
flame  cuts  off  sharply,  this  indicates  that  the 
remaining air has been dispersed. 

 

 

Set the pump pressure to the correct level. Run the 
boiler  for  15  minutes  and  measure  CO

2

  levels  at 

the  flue  gas  sample  port  (

page 28

).  Compare  the 

readings  with  those  given  in  the  burner  setup 
leaflet and if necessary adjust the intake of air into 
the burner. 

 

 

Check 

the 

smoke 

number 

and 

flue 

gas 

temperature. 

 

 

If the boiler is not going to be put to immediate use, 
isolate the oil and electrical supplies. If the boiler is 
not  going  to  be  run  during  freezing  conditions,  the 
system should be drained of water. 

 

 

Handing over 

 
After  completing  the  boiler  installation,  the  engineer 
should check the system to ensure it is satisfactory and 
works  according  to  these  instructions.  The  use  of  the 
boiler 

and 

other 

system 

controls 

should 

be 

demonstrated to the end user. 
 
All  instructions  should  be  handed  to  the  user  for 
retention. Advice should be given on the requirement  

 
 
for  an  annual  service.  For  householder  reference,  the 
form on 

page 35

 should be completed. 

 
A  CD/10  installation  completion  form  (or  non-OFTEC 
equivalent)  should  be  completed  and  a  copy  left  with 
the  end-user.  The  registration  card  should  be 
completed  in  full  and  returned  to  TR  Engineering. 
Failure  to  do  so  may  delay  any  subsequent  warranty 
work. 
 
All  installations  must  be  registered  with  the  local 
authority's  Building  Control,  either  through  OFTEC  or 
directly  through  Building  Control. 

This  is  a  legal 

requirement

.  After  registration,  the  local  council  will 

issue a Works Notification Certificate. 
 

SERVICING 

 
To maintain the boiler's high thermal efficiency

—and to 

ensure  continued,  reliable  operation

—the  boiler 

must

 

be serviced annually by a qualified engineer, preferably 
OFTEC-trained  and  registered.  Any  electrical  work 
should be carried out by a suitably qualified engineer. 
 
A  CD/11  commissioning  form  (or  non-OFTEC 
equivalent)  should  be  completed  and  a  copy  left  with 
the  end-user.  The  CD/11  enables  the  engineer  to 
demonstrate  compliance  with  building,  health  and 
safety, and efficiency requirements. 
 
If  the  boiler  provides  central  heating  and  hot  water  all 
year  round,  the  best  time  for  the  annual  service  is  just 
before the start of the heating season. 
 
Before starting the service, review the health and safety 
information on 

page ii

 

Pre-service checks 

 

 

Ensure the air inlets on the flue terminal are clear. 

 

 

Ensure the external controls are working. 

 

 

Ensure  the  ventilation  openings  are  clear  and 
adequate for the size of the boiler (

pages 10

–11

). 

 

 

Ensure all water and oil connections are secure. 

 

 

Inspect the flexible oil lines; replace if necessary. 

Summary of Contents for EuroStar Band A

Page 1: ...29 36kW For Balanced or Conventional Flue OPERATION INSTALLATION COMMISSIONING SERVICING INSTRUCTIONS Please read these instructions carefully before installing commissioning and using this appliance...

Page 2: ...other exposed areas When disposing of materials limit dust and the risk of inhalation by using a water spray Ensure materials are securely wrapped Seek urgent medical attention if inhaled or ingested...

Page 3: ...cations 9 Installation 10 Regulations Health Safety 10 Siting 10 Ventilation 10 11 System design 12 Electrical supply wiring diagram 12 Condensing system 13 Oil 14 Storage protection 14 Supply 14 15 F...

Page 4: ...ntrol thermostat fig 1 allows selection of water temperatures at five positions between 55 C and 82 C Where a cylinder thermostat is also fitted to the system ensure that the boiler thermostat is set...

Page 5: ...pe adversely affecting the operation of the burner and potentially reducing the life expectancy of the oil pump After an oil delivery allow half an hour for the oil to settle in the tank before using...

Page 6: ...arty will not be accepted unless authorised in advance by TR Engineering Ltd Technical Assistance A team of trained technical advisors is available to discuss any problem with the appliance In many ca...

Page 7: ...TR Engineering balanced flue kit it becomes a room sealed appliance These kits allow the boiler to be installed in a wide variety of site conditions The balanced flue is available in horizontal high...

Page 8: ...FIG 3 FIG 4 15 26 29 36 A 460 460 B 854 895 C 597 672 D 355 404 E 603 660 F 693 761 G 743 821 H 16 16 J 60 60 K 37 37 L 197 198 M 85 85 N 71 71 P 231 231...

Page 9: ...22mm compression Conventional Flue Socket 4 100mm Maximum Operating Pressure 3 bar 43 5 psi Test Pressure 4 5 bar 65 3 psi Starting Current 3 5 amp Running Current 0 77 amp Control Thermostat Adjusta...

Page 10: ...le base that is capable of supporting the installed weight of the boiler including its water content Sound levels While the low sound level of the boiler makes it suitable for utility room or kitchen...

Page 11: ...FIG 5 Conventional Flue FIG 6 Balanced Flue...

Page 12: ...etween 20 C and 30 C Electrical supply All electrical wiring must be carried out by a qualified electrician in accordance with current IEE Regulations and any local regulations that apply The boiler m...

Page 13: ...rom the boiler on a minimum fall of 1 20 fig 9 Insulate any external pipework to prevent the condensate from freezing DO NOT use copper pipework for the condensate drain If the boiler is installed bel...

Page 14: ...of a leak The tank capacity exceeds 2 500 litres Supply A long life flexible oil hose is supplied with the boiler A filter and shut off valve are also required These should be fitted in the positions...

Page 15: ...0 0 5 1 0 1 5 2 0 3 0 3 5 8mm ID Supply Maximum Run Metres 35 30 25 20 15 8 6 10mm ID Supply 100 100 100 90 70 30 20 FIG 10 Lift H 0 5 1 0 1 5 2 0 8mm ID Supply Maximum Run Metres 10 20 40 60 10mm ID...

Page 16: ...ffected by high wind conditions as the wind pressures are applied equally to both the air intake and flue gas discharge sections creating the balanced condition Balanced flue condensing boilers are al...

Page 17: ...rnal corner 300 600 N From a vertical structure to one side 750 G Above ground or balcony level 300 600 O Above a vertical structure less than 750mm to one side 600 Scotland P From a ridge terminal to...

Page 18: ...e heat exchanger and secure in position using the four nuts previously removed Adjust the terminal length as required ensuring a minimum distance of 140mm is kept from the end of the terminal to the e...

Page 19: ...Model Dim A 15 20 746mm 20 26 746mm 29 36 794mm Model Dim A 15 20 746mm 20 26 746mm 29 36 794mm 2334 600mm Horizontal Balanced Flue Kit 2335 1000mm Horizontal Balanced Flue Kit FIG 17 FIG 18...

Page 20: ...suring a minimum distance of 140mm is kept from the end of the terminal to the external face of the wall Seal the outer horizontal sections together with a suitable material See figs 21 22 for allowab...

Page 21: ...ion 222820 1 5 Spigot Sealing Plate 222825 1 6 Spigot 222819 1 7 Sealing Plate Gasket 223198 1 8 Flue Sealing Plate 223191 1 9 O Ring Seal 221647 2 Item Description Part No Kit 2355 Part No Kit 2356 Q...

Page 22: ...600mm Horizontal Balanced Flue kit Model A B 15 20 1892 1038 20 26 1892 1038 29 36 1940 1046 2357 High Level Adaptor Kit used with 2356 1000mm Horizontal Balanced Flue Kit Model A B 15 20 1892 1038 20...

Page 23: ...us sections in the same manner Note Both instances of item 7 can be discarded if they are not required Of the main flue lengths only 6 8 are mandatory Fit the terminal extension 9 over the preceding f...

Page 24: ...Spigot Sealing Plate 222825 1 5 O Ring Seal 221647 6 6 Flue Lower Section 222820 1 7 Flue Middle Section 222829 2 8 Flue Top Section 222877 1 9 Terminal Lower Section 222880 1 10 Terminal 222850 1 11...

Page 25: ...ed sections Longer runs can be achieved by purchasing additional sections of pipe Permanent obstructions may be avoided by the use of 45 elbows See page 26 for details A B C Min Max 15 20 4600 1390 37...

Page 26: ...0mm each to the calculation The 90 bend in the vertical balanced flue kit contributes 1000mm The 45 elbows can be used to offset the vertical sections of flue on both the high level and vertical flue...

Page 27: ...e oil and electrical supplies If the boiler is not going to be run during freezing conditions the system should be drained of water Handing over After completing the boiler installation the engineer s...

Page 28: ...er emerges from the drainage pipe Replace the baffle strips ensuring each is firmly pushed into the flue ways See figs 28 29 Burner and combustion chamber Ensure the electrical supply is switched off...

Page 29: ...below The use of a tool may be required to lift the third baffle 3 from the combustion chamber Insert a screwdriver or similar into the lifting hole in the centre of the baffle and raise above the li...

Page 30: ...will result in incorrect combustion and may Invalidate the appliance warranty Secondary Baffles Correct placement of the secondary baffles is crucial to the boiler s efficient operation Turn the baffl...

Page 31: ...ulty photocell or photocell not seeing flame Clean photocell check for damage ensure it is fully inserted replace as necessary Low oil pressure Check pump pressure and adjust Morning start lock out Fa...

Page 32: ...FIG 30 Burner Fault Finding Logic Chart...

Page 33: ...ottom baffle 1 224608 1 224729 1 16 Condensing unit spiral baffle 1 224589 18 224589 13 16 Condensing unit blade baffle 1 224735 5 17 Combustion chamber access cover 224670 1 224690 1 18 Access cover...

Page 34: ...FIG 31 Boiler Assembly...

Page 35: ...The following information should be provided upon installation of the appliance for householder reference Installation Engineer Company Company Address Company Tel No...

Page 36: ...strations contained within are vested in TR Engineering Ltd And neither the brochure or any part thereof may be reproduced without prior written consent TR Engineering s policy is one of continuous re...

Reviews: