FAULT
POSSIBLE CAUSE
ACTION
POOR FLAME CUT-OFF
Air in pump or at back of nozzle
Bleed pump through pressure gauge port,
also check for leaks in oil line if 2-pipe system
Oil contaminated with water
Run off oil at burner until free of water and
drain condensation from tank.
Dirt in solenoid valve
Clean or replace valve.
Pump shut-off piston sticking
Replace pump.
MORNING START LOCK-OUT
Faulty non-return valve or air leak
Replace none-return valve and cure leak.
in two pipe system.
Low voltage
Check with local Electricity Board.
Combustion readings incorrect
Check combustion under normal running
conditions and compare readings with
those given on page 16.
Oil level in tank falling below
Raise tank or fit a 2-pipe system.
burner.
Nozzle partially blocked
Replace nozzle
Oil pressure too low
Check and recommission
Flue blocked or damaged
Check and rectify
Pump coupling loose or worn
Check and replace
BURNER STARTS VIOLENTLY
Delayed ignition
Check electrode setting and adjust to correct gap
Check electrodes for damage
Check H.T. leads for damage and positive connection
20
FAULT FINDING (continued)
DELAYED IGNITION -
BURNER PULSATES ON
START UP