9. FAULT FINDING
Burner
ELECTRICITY SUPPLY - before making any electrical checks, switch off mains supply to boiler.
FAULT
POSSIBLE CAUSE
ACTION
BURNER FAILS TO
Control box locked out - Light on
Press control box reset button NB only try twice
START
Limit-stat tripped
Press reset button under control panel and
check function of boiler control thermostat.
Boiler thermostat or other system
Ensure all controls are calling for heat.
controls satisfied.
Fuse blown
Fit new 5 amp fuse, if it blows again,
check for short circuit in wiring.
Check for live supply continuity
If live supply confirmed,
up to burner
change control box.
Motor or pump seized
Check for rotation and replace as
necessary.
No oil supply
Check oil level in tank and feed to burner.
Photo-cell not seeing flame
Clean photo cell and ensure it is fully plugged in.
Air trapped in pump
Bleed air through pressure gauge tapping.
Solenoid valve faulty
Check coil for continuity and replace if faulty.
Nozzle blocked
Replace nozzle with one of same specification.
Electrodes incorrectly set
Reset gap and position electrodes as shown in
burner diagram.
Electrode insulator cracked
Check and replace if insulator cracked
or crazed.
Ignition transformer and H.T.
Check for spark and condition of
leads faulty contacts
H.T. contacts. Replace as necessary.
Low oil pressure
Check pump pressure and adjust to correct setting.
Oil contaminated with water
Run off oil at burner until free of water and
drain condensation from tank.
Oil filter partially blocked
Wash filter clean with kerosene.
Photo cell fault
Clean photo-cell and ensure it is fully plugged in.
Replace if faulty.
Oil pressure low
Check pump pressure and adjust to
correct setting.
33
BURNER STARTS
BUT FLAME NOT
ESTABLISHED
FLAME ESTABLISHED
BUT BURNER LOCKS
OUT AFTER FEW
SECONDS
Summary of Contents for Combi 50 ECO
Page 10: ...7 Fig 2...
Page 14: ...11 Fig 4 EUROSTAR COMBI SCHEMATIC LAYOUT Fig 5 SEALED SYSTEM PIPING SCHEMATIC DIAGRAM...
Page 20: ...17 Fig 11 SINGLE PIPE OIL SUPPLY HEAD H METRES...
Page 21: ...18 Fig 12 TWO PIPE OIL SUPPLY...
Page 22: ...19 Fig 13 DE AERATED OIL SUPPLY INSTALLATION...
Page 32: ...29 Fig 20 2273 VERTICAL B F KIT 2273 Vertical Balanced Flue Kit 600mm 24 3000mm MAX 118...