TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 5, 07-Mar-2016. 1

Installation Instructions

TB/TI

Thermistor Insertion Temperature Sensor

Important: Retain these instructions

These instructions shall be used by trained service 

personnel only. 

If the equipment is used in a manner not 

specified by these instructions, the protection provided by the 

equipment may be impaired.

https://partners.trendcontrols.com

1

Dimensions

2 InSTallaTIon

Box ConTenTS

TB/TI Thermistor Insertion 

Temperature Sensor Installation 

Instructions (TG200727)

6 m

m (

0.

24

”)

400 mm (15.75”)

94 m

m (

3.

70

”)

57 mm (2.24”)

11

3 m

m (

4.

45

”)

50 m

(1

.9

7”

)

6 mm compression 

fitting

3 x 4 mm diam. holes 

on a 30  mm (1.18”) PCD

(Pitch Circle Diameter)

Mounting flange for use as duct sensor (ACC/DF)

clip

brass brush

hexagonal 

socket 2 mm 

grub screw

Universal Fitting Kit for immersion sensor 

use in existing pockets (ACC/UF)

spring

Pockets for use as immersion sensor: Brass (WB150 or WB50); Stainless Steel (WS150 or WS50)

135 mm (5.31”)

14 mm 

(0.53”)

24 mm 

(0.95”)

Ø8 mm 

(0.31”)

143 mm (5.63”)

Ø6.5 mm (0.25”)

G½” (BSPP)

ConTenTS

Box Contents .................................................................1

2 Installation .....................................................................1

Cleaning and Maintenance

 ...........................................7

4 Disposal .........................................................................8

150 mm (5.91”)

70 mm (2.76”)

50 mm (1.97”)

58 mm (2.28”)

WB150, WS150

WB50, WS50

TB/TI/ES

TB/TI/S

TB/TI/L

Summary of Contents for Thermistor TBTI

Page 1: ...ature Sensor Installation Instructions TG200727 6 mm 0 24 400 mm 15 75 94 mm 3 70 57 mm 2 24 113 mm 4 45 50 mm 1 97 6 mm compression fitting 3 x 4 mm diam holes on a 30 mm 1 18 PCD Pitch Circle Diamet...

Page 2: ...therwise use averaging sensor 40 C 40 F 50 C 122 F to 40 C 40 F 110 C 230 F to Duct Duct H O 2 0 RH 95 RH Protection IP67 NEMA6 Ensure no stratification e g downstream of mixing valves junctions d 40...

Page 3: ...et length clip engages in groove probe is forced against end of pocket tighten screw over bush InSTall SenSoR InTo PoCKeT If using Universal Fitting Kit if pocket has clip retaining groove push clip o...

Page 4: ...ST DEPTH OF PROBE drill 3 holes screw on flange mounted flange 7 mm 0 28 42 5 mm 1 67 85 mm 3 35 2 off 2 off No 6 3 4 s s self tapping screws integral foam gasket compression fitting duct mounting fla...

Page 5: ...20x1 5 cable gland supplied Or use M20 flexible conduit not supplied Recommended cable TP 1 1 22 HP 200 600V Belden 8761 Terminal size 0 5 to 2 5 mm2 20 to 14 AWG Sensor IQ controller COM 0V IN polari...

Page 6: ...he following SET Unique Sensor References should be used Thermistor Thermistor TBTI 30 C to 110 C Thermistor TBTI F 22 F to 230 F Alternatively set scaling mode to 5 characterise and enter scaling man...

Page 7: ...7 Issue 5 07 Mar 2016 7 Installation Instructions TB TI There are no serviceable parts inside the unit Cleaning of the unit should be carried out in order to avoid buildup of dust or other containment...

Page 8: ...e Switzerland by its Authorized Representative Trend Control Systems Limited Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the conte...