TB/TS/KO, /OS, /KOS, /KOF, /KOSF Sensors Installation Instructions TG200606 Issue 2, 08/03/2011 3
Installation Instructions
TB/TS/KO, /OS, /KOS, /KOF, /KOSF
InSTallaTIOn
(continued)
Wire to controller
7
* For /KO or /KOF connect Status/Power to 10 Vdc or
24 Vdc; if using /KOS, /OS, /KOSF as /KO or /KOF, the
Status/Power input should be powered from 10 Vdc e.g.
via dummy analogue output.
** For /OS option also connect knob (the knob input will
supply the override circuit).
*** Note that /KO, /OS, /KOS, /KOF, /KOSF cannot be
used by IQ211 (although they can be used by IQ212)
IQ Configuration Manual 90-1533
IQ3 Configuration Manual
TE200768
TB/TS Data Sheet TA200603
Set up special IQ strategies
9
or
For /KO, /OS, /KOS, /KOF, /KOSF special
override and status strategies.
For /KOF, /KOSF special strategy for fan speed
input on IQs
Legend
Switch position
Voltage
Nominal
Recommended
Fan Off
0V
Fan low speed
2.8V
>2 V
Fan medium speed
5.6V
>4.5 V
Fan high speed
8.5V
>7 V
Automatic
9.7V
>9 V
0 V
Temperature
Status/Power
Knob
+24 V
Fan
1
2
4
3
5
6
IN
OUT
0 V
IN
COM (0 V)
+24 V
IN
COM (0 V)
SENSOR
IQ
TB/TS
/K, /O
/S
/F
linked for thermistor (T)
analogue input
auxiliary supply
COM (0V)
analogue output
analogue input
see note ** below
analogue input
linked for thermistor (T)
linked for voltage (V)
linked for voltage (V)
1 2 3 4 5 6
Note that these options (TB/TS/KO,
/OS, /KOF, /KOSF) cannot be used
with IQLs; use options TB/TS,
TB/TS/K, /KE, or /KEF with IQLs.
OpTIOn
cOnnEcT
TERMInalS
TB/TS
1, 2
TB/TS/K
1, 2, 3
TB/TS/KO***
1, 2, 3, 4*
TB/TS/OS***
1, 2, 3**, 4
TB/TS/KOS***
1, 2, 3, 4
TB/TS/KOF***
1, 2, 3, 4*, 5, 6
TB/TS/KOSF***
1, 2, 3, 4, 5, 6
Terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
Note that the IQ recommended limits may need to be changed to suit mains supply voltage and
auxiliary supply loading, or a 24 Vdc regulated supply can be used.
assemble unit
8
‘click’