TB/TS/KO, /OS, /KOS, /KOF, /KOSF Installation Instructions TG200606 Issue 3, 26-Aug-2014
TB/TS/KO, /OS, /KOS, /KOF, /KOSF
Installation Instructions
Please send any comments about this or any other Trend technical publication to [email protected]
© 2014
Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
Trend Control Systems limited
Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com
Trend Control Systems USa
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 897-3900 Fax:(425) 869-8445 www.trend-americas.com
11
Test system
10
Set up IQ Sensor Types
4 DISPOSal
Weee Directive:
At the end of their useful life the packaging and
product should be disposed of by a suitable
recycling centre.
Do not dispose of with normal household waste.
Do not burn.
For IQ2 version 2.1 or greater, IQ3, IQ4, and IQeco, the
recommended method of setting the sensor scaling is to use
the ‘Unique Sensor Reference’ provided in SET, see below
for details.
For IQ1, IQ2 Version 2.0 or lower, see Sensor Scaling
Reference Card TB100521A, and set up manually in SET.
The input channel must be set to the appropriate input type (see controller documentation for details) and the sensor
type module must be set up with the correct scaling. If the SET pre-defined strategy is used the sensor scaling will
have been set up.
-
+
/K
/O
/F
/OS
∆
T
∆
SP
∆
yellow
green
3 InSTallaTIOn
(continued)
Knob:
The input channel used should be set for thermistor
(T), and sensor scaling set as below.
Controller
Unique Sensor Reference
notes
IQ1, IQ2 v2.0
or lower
Set up manually in SET
IQ2 v2.1 or
greater, IQ3,
and IQ4
Knob TB 3 deg trim
Guaranteed ±3
trim
Knob T 3 deg trim
±3 ±20% linear
trim
IQeco
(Knob TB 05 deg trim)
Type 102 - Potentiometer
-0.5 to + 0.5
deg trim
Thermistor:
The input channel used should be set for
thermistor (T), and sensor scaling set as below.
Controller
Unique Sensor Reference
notes
IQ1, IQ2 v2.0
or lower
Set up manually in SET
IQ2 v2.1 or
greater, IQ3,
and IQ4
Thermistor TBTS
Value in °C
Thermistor TBTS F
Value in °F
IQeco
(10k Therm DegC TBTS)
Type 101 - Thermistor °C
Value in °C
(10k Therm DegC TBTS)
Type 108 - Thermistor °F
Value in °F
Fan Control:
The input channel should be set for voltage (V),
and sensor scaling set as below.
Controller
Unique Sensor Reference
notes
IQ2 v2.0 of
lower
Set up manually in SET
IQ2 v2.1 or
greater, IQ3,
and IQ4
Fan Control V
produces
range 0 to 9.7
Fan KO enum
produces fan
speed settings
for /O sensors
- see TB/TS
data sheet
IQeco
(Fan TBTS KOF)
Type 111 - TBTS Fan Speed
Control
For TBTS
KOF, KOSF