background image

IQ4E/.. Installation Instructions - Mounting TG201338 Issue 4, 19-Jan-2016. Applies to v3.33. 1

Installation Instructions - Mounting

IQ4E/..

Controller

Important: Retain these instructions

These instructions shall be used by trained service 

personnel only. 

If the equipment is used in a manner not 

specified by these instructions, the protection provided by the 

equipment may be impaired.

https://partners.trendcontrols.com

GB

DE

DK

FI

ES

FR

IT

NL

NO

RU

PL

SE

1

Dimensions

WARNING 

Removal of cover exposes dangerous 

voltages.

WARNING 

To reduce the risk of electrical shock or fire 

do not interconnect the output of different Class 2 circuits.

It  is  recommended  that  the  installation  should  comply 

with the local electrical safety installation practices (e.g. 

HSE Memorandum of Guidance on Electricity at Work 

Regulations 1989, USA National Electric Code).

Any connected devices must be insulated from mains by 

reinforced insulation.

3 INsTAllATIoN

Box CoNTENTs

2 sToRING

CoNTENTs

Box Contents .................................................................1

2 Storing ...........................................................................1

3 Installation .....................................................................1

Note: For temperatures below 0°C (32°F) special care must be 

taken that there is no condensation on or within the unit.

IQ4E/.. Installation 

Instructions - Mounting 

(TG201338)

IQ4/IC/TERM

I/O Bus Terminator

Removing From DIN Rail ............................................11

Field Maintenance .......................................................12

6 Disposal .......................................................................12

End User Licence Agreement .....................................12

labels used on IQ4E

!

Caution, consult 

documentation

Caution, possibility 

of electric shock

230 Vac input 

power connector
RS232 Local 

Supervisor Port

 

Wallbus 

connector

Auxiliary supply 

output connector

n n

n

Universal input 

connector

USB 

(for future use)

Terminator switch 

(/XNC only)

Bias switch 

(/XNC only)

RS-485  

(/XNC only)

Ethernet indicators 

and connector

84

85

86

87

Trend current 

loop connector

Auxiliary supply 

output connector

n

n

n

Analogue output 

connector

USB Local 

Engineering Port

Service button/

indicator

Power indicator

Watchdog indicator

LAN OK indicator

I/O Bus indicator

192.5 mm (7.55”)

58.5 mm (2.3”)

53.5 mm (2.11”)

11

0 m

m (

4.

33

”)

11

6 m

m (

4.

57

”)

H O

2

+60°C

(+140°F)

-25°C

(-13°F)

90%RH

Summary of Contents for IQ4E

Page 1: ...reinforced insulation 3 Installation 1 Box Contents 2 Storing Contents 1 Box Contents 1 2 Storing 1 3 Installation 1 Note For temperatures below 0 C 32 F special care must be taken that there is no co...

Page 2: ...tinued Must be installed in an enclosure rated to at least IP20 or equivalent Note For temperatures below 0 C 32 F special care must be taken that there is no condensation on or within the unit Protec...

Page 3: ...structions Mounting IQ4E 3 Mount Unit on DIN Rail 4 Attach large Barcode label to Panel 5 open Rotating Covers 3 INsTAllATIoN continued I QECO Q3 B_ X7 3 0 8 0 0 3 1 SERIAL No IQ4e Q3B_X73080031 TREND...

Page 4: ...0 C or greater This equipment must be earthed grounded 230 230 Vac 10 50 60 Hz at up to 70 VA The 230 V supply must include a dedicated 5 A fuse complying with IEC60269 BS1362 and a suitably rated swi...

Page 5: ...5 lb in TP 1 1 22 HF 200 Belden 8761 cable recommended for all inputs outputs Screened cable is not generally required unless the cable passes through electrically noisy environments Where it is used...

Page 6: ...equired 11 Connect Auxiliary Supply Output s if required 3 Installation continued Output voltage 0 to 10 Vdc Maximum current 20 mA source 3mA sink Output voltage 24 Vdc 5 Maximum current Terminals 70...

Page 7: ...ystem 4 wire system T R T R T R T R panel enclosure ground T R R X T Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Maximum cable length depends on cab...

Page 8: ...nnection to an RS 485 4 wire system a suitable 2 to 4 wire converter will be required RS 232 system RJ12 FFC68 Plug Local Supervisor Port 1 RX 2 NC 3 CTS 4 RTS 5 GND 6 TX TX RX RTS CTS GND pin 1 Note...

Page 9: ...d Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Cable type Unscreened twisted pair Maximum cable length 60 m 200 ft in total used to connect all wallb...

Page 10: ...rigid interconnectors Maximum number of I O modules on I O bus IQ4 IO Installation Instructions Mounting TG201338 XCITE IO Installation Instructions Mounting TG200627 cable interconnection XCITE CC c...

Page 11: ...ose Rotating Covers 17 Close Panel Enclosure 18 Configure IQ4E Controller and I O Modules 1 Remove from DIN rail 3 INsTAllATIoN continued IQ4E Installation Instructions Configuring TG201339 IQ4 IO Ins...

Page 12: ...end Control Systems Ltd s software suppliers HAS RELIED UPON Trend Control Systems Ltd TO CONDUCT SUFFICIENT TESTING TO DETERMINE THAT THE SOFTWARE IS SUITABLE FOR SUCH USE NO WARRANTIES FOR THE SOFTW...

Reviews: